Troubleshooting Guide

Trouble 3

The Compressor/Outdoor Fan don't operate

Turn on the main power.

Operate Cooling Mode by setting the disired temperature of the remote controller to less than one of the Indoor temperature by 1°C(33.8°F) at least.

When in air circulation mode, compressor/outdoor fan is stopped.

Check that the sensor for Indoor temperature is attatched and as close as to the Heat Exchanger (Evaporator.)

When the sensor circuit for Indoor temperature and connector have a bad connection or are not engaged, Compressor/Outdoor fan is stopped.

• Check the related circuit of R01H(1K), R02H(1K), R03H(1K), R04H(1K), Micom(pin No. 74 , 75 , 76 , 77 ).

• Check that the Indoor temperature sensor is disconnected (about 10K at 25°C(77°F)).

Check the Relay(RY-PWR, RY-START) for driving Compressor.

Check the voltage between brown and blue cable of terminal which connects to the Outdoor unit (About AC208V / 230V).

Check the Outdoor PCB Assembly's relay circuit.

Check Point

Comp. ON

Comp. OFF

Between Micom(No. 50,51) and

DC 5V

DC 0V

GND

 

 

Between IC01M(No. 10) and

DC 1V

DC 12V

GND

 

 

 

 

 

Turn off main power.

Check the electrical wiring diagram of Outdoor side.

Check the open or short of connecting wires between Indoor and Outdoor.