Installation

Piping length and elevation

Multi Piping Type

 

Max total length

Max length of

Min length of

Max Elevation

Max elevation

 

between each

Capacity

of all pipes

each pipe

 

each pipe

 

between indoor

 

 

indoor unit and

 

(A+B/A+B+C)

 

(A/B/C)

 

(A/B/C)

 

outdoor unit (h1)

units (h2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18 kBtu

30 m (100 ft)

15 m (50 ft)

 

3 m (10 ft)

 

7.5 m (25 ft)

 

7.5 m (25 ft)

 

 

 

 

 

 

 

 

 

 

 

 

 

24 kBtu

30 m (100 ft)

15 m (50 ft)

 

3 m (10 ft)

 

7.5 m (25 ft)

 

7.5 m (25 ft)

 

 

 

 

 

 

 

 

 

 

 

 

 

36 kBtu

45 m (150 ft)

15 m (50 ft)

 

3 m (10 ft)

 

7.5 m (25 ft)

 

7.5 m (25 ft)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pipe Size

 

 

 

 

Indoor Capacity

 

 

 

 

 

 

 

 

 

 

 

 

Gas

 

 

Liquid

 

Standard Length

 

 

Additional

 

 

 

 

 

 

 

Refrigerant

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9 kBtu

 

9.52 mm (3/8")

 

6.35 mm (1/4")

 

7.5 m (25 ft)

 

20 g/m (0.22 oz/ft)

 

 

 

 

 

 

 

 

 

12 kBtu

 

9.52 mm (3/8")

 

6.35 mm (1/4")

 

7.5 m (25 ft)

 

20 g/m (0.22 oz/ft)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18 / 24 kBtu/h

h1

A

B

h1

B

36 kBtu/h

h2

h1

A

B

C

h1

h1

h2

h2

CAUTION: Capacity is based on standard length and maximum allowance length is on the basis of reliability.

- 21 -

Service Manual

Page 21