Charging

Charging

Charging

Each outdoor unit is factory charged (nameplate charge) for the evaporator as well as a 7.5m(25ft) line set for each indoor line.

Any time total line set is used either shorter or longer then the nominal 15m(50ft) line set length the refrigerant charge has to be adjusted.

Whether the line set is made shorter or longer you must adjust the charge based on how many ft of tubing are either added or removed based on 20g/m(0.22oz/ft) of R-410A per meter(foot).

 

Max total length

 

 

Max Elevation

Max elevation

Additional

 

Max length of

Min length of

between each indoor

Capacity (Btu/h)

of all pipes

between indoor

 

(A+B)

each pipe (A/B)

each pipe (A/B)

unit and outdoor unit

units (h2)

Refrigerant

 

 

 

(h1)

 

 

 

 

 

 

 

18k

30m(100ft)

15m(50ft)

5m(16ft)

7.5m(25ft)

7.5m(25ft)

20g/m(0.22oz/ft)

 

 

 

 

 

 

 

Example: A 75ft line set is used for dual - zone 25 additional ft X 0.22 ounces per foot= add 5.5 ounces of R- 410A

Important:(Unit is critically charge)

If you are ever uncertain of the unit charge, reclaim, evacuate and weigh in the correct charge using the unit name- plate charge adjusting for line sets longer or shorter than 7.5m(25ft) for each indoor unit.