FunctionofOutdoor Unit

Operation

 Operating Step LEV ControlFunction Out door Fan Controlof R/Valve Control(Heating Model Only)Outdoor Unit Defrost Function Oil Return System Comp Overload Protection High Pressure ProtctionManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background

Outdoor Unit

Manual background Operating Step

Compressor step varies considering condition such as room temp,outdoor temp, operating room number,Temp gap between room temp and set temp and so on.

Manual background LEV Control

LEV pulse is modulated to keep constant superheat or subcooling.

Manual background Out door Fan Control

Outdoor fan operates at High or Off to respond to the load condition.

Manual background R/Valve Control(Heating Model Only)

Convert R/Valve to change cooling to heating, heating to cooling.

Manual background Defrost Function

After 45 min heating operation, check the defrost condition and if outdoor pipe temp is below -

5°C(23°F) and released from deice operation in case outdoor pipe temp is over 12°C(53.6°F) or 9 min cooing mode.

To deice outdoor heat exchanger in low temp condtion, convert operating mode from heating to cooling mode.

Manual background Oil Return System

In single(one) comp operation duration, another comp will operate for 30 seconds every 1 hours.

Manual background Comp Overload Protection

To protect comp from being overload, protector will turn off the comp.

Manual background High Pressure Protction

If cycle pressure is too high(around 36.7 kgf/cm2), it will turn off comp A

Service Manual 41

Page 41
Image 41
Heat Controller DMH18DB-1 FunctionofOutdoor Unit, Operation, Service Manual, Operating Step, LEV Control, Defrost Function