Capacitor error

Troubleshooting Guide

Error

Title

 

Cause of error

Check point & Normal condition

 

code

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Discharge sensor

• Check the discharge pipe sensor.

 

33

D-Pipe Temp. High

 

• Check the install condition for over load.

 

 

temp. high

• Check the leakage of refrigerent.

 

 

 

 

 

 

 

 

 

 

 

 

• Check the SVC V/V open.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

115°C(239°F)

 

COMP OFF

 

 

 

 

 

 

 

 

 

 

 

LEV OPEN(16PULSE/MIN)

 

 

 

100°C(212°F)

 

 

 

 

 

 

 

 

 

 

 

 

LEV OPEN(10PULSE/MIN)

 

 

 

95°C(203°F)

 

 

 

 

 

 

 

 

 

 

 

 

NORMAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check Point

1.Check the install condition for over load.

2.Check the SVC V/V open.

3.Check the leakage of refrigerent.

4.Check the constant compressor.

Error

Title

Cause of error

Check point & Normal condition

code

 

 

 

 

 

 

 

51

Capacitor error

• Over Capacitor com-

• Check the indoor unit capacity.

bination

• Check the combination table

 

 

 

 

 

 

Check Point

1.Check the indoor unit capacity.

2.Check the combination table.

In the tropical model case

single cycle has no error for over capacity.