Trouble 5 When the louver does not operate.

Troubleshooting Guide

Trouble 5 When the louver does not operate.

When Vertical Louver does not operate.

Confirm that the Vertical Louver is normally geared with the shaft of Stepping Motor.

If the regular torque is detected when rotating the Vertical Louver with hands When Vertical Louver does not operate. Normal

Check the connecting condition of CN-UP/DOWN Connector

Check the soldering condition(on PWB) of CN-UP/DOWN Connector

Check the operating circuit of the Vertical Louver

Confirm that there is DC +12V between pinManual background(RED) of CN-UP/DOWN and GND.

Confirm that there is a soldering short at following terminals. - Between 60 , 61 , 62 and 63 of MICOM

- Between 2

, 3

, 4

and 5 of IC01M

- Between 12 , 13

, 14 , 15 of IC01M

- Between 1

, 2

, 3

, 4 and 5 of CN-UP/DOWN

If there are no problems after above checks

Confirm the assembly conditions that are catching and interfering parts in the rotation radial of the Vertical Louver

Service Manual 61