Trouble 4 When indoor Fan does not operate.

Troubleshooting Guide

Trouble 4 When indoor Fan does not operate.

When indoor Fan does not operate.

Does the voltage of each terminals of CN-MOTOR CONNECTOR in

Indoor unit corresponds to values in the Table of page 69

Does the voltage of terminal of CN-DC/DC CONNECTOR in Indoor unit corresponds to the values in the table of page 56

Check connecting condition of the CN-MOTOR CON-

NECTOR

Do the voltage of terminal of CN-DC/DC CONNECTOR in Outdoor unit corresponds to the values in the table of page 56

Check the pattern and the condition of Indoor unit PWB Ass'y.

Check the interference of Indoor Fan.

NO

Check the patterns and the conditions of outdoor unit PWB Assy's.

Check the connecting condi- tion and disconnection of connecting wires between Indoor and Outdoor unit.

Check the motor of Indoor Fan

When indoor Fan does not operate. Indoor Fan may be stopped in the Soft Dry Mode(change to the Cooling Operation Mode).

60Multi type Air Conditioner Indoor Fan is to be stopped when Indoor pipe(coil) termperature is lower than 79°F. (At that times, Defrost indicator is turned on)

60Multi type Air Conditioner