ELECTRICAL - LOW VOLTAGE WIRING

Installation, Operation & Maintenance

HEV/H SERIES

Heat Controller, Inc.

 

 

 

ELECTRICAL - LOW VOLTAGE WIRING

Thermostat Connections

The thermostat should be wired directly to the DXM2 board. See “Electrical – Thermostat” for specific terminal connections.

Figure 21: Low Voltage Field Wiring

 

 

Capacitator

 

 

Circ Brkr

Grnd

Loop PB1

HWG PB2

 

 

Contactor - CC

 

 

Low Water Temperature Cutout Selection

The DXM2 control allows the field selection of low water (or water-antifreeze solution) temperature limit by clipping jumper JW3, which changes the sensing temperature associated with thermistor LT1. Note that the LT1 thermistor is located on the refrigerant line between the coaxial heat exchanger and expansion device (TXV). Therefore, LT1 is sensing refrigerant temperature, not water temperature, which is a better indication of how water flow rate/temperature is affecting the refrigeration circuit.

The factory setting for LT1 is for systems using water (30°F [-1.1°C] refrigerant temperature). In low water temperature (extended range) applications with antifreeze (most ground loops), jumper JW3 should be clipped as shown in Figure 19 to change the setting to 10°F [-12.2°C] refrigerant temperature, a more suitable temperature when using

an antifreeze solution. All residential units include water/ refrigerant circuit insulation to prevent internal condensation, which is required when operating with entering water temperatures below 59°F [15°C].

BR

Transformer

DXM 2

Figure 22: LT1 Limit Setting

Fault Status

HP

LP

LP

LT1

LT1

CB

Low Voltage

Connector

Rev.: 3/24/00

c1 ay

c2 ay

Off On

Figure 21: Low Voltage Field Wiring1 2 3 4

S3 Off On

DXM2 PCB1 2 3 4 5 6 7 8

S1

Off On

Manual background1 2 3 4 5 6 7 8

S2

A0-1 A0-2

Manual background JW3

CCH

Relay

LT2

LT2

RV

RV

CO

12 CO

RV P7 Relay

1 24Vdc

EH1

4 EH2

Comp P6

Relay

CCG

P11P10

AO2 Gnd T1 Manual background T2 Manual background T2 Manual background T3 Manual background T3 Manual background T4 Manual background T4

P9 CC

T5 Manual backgroundT5 Manual background T6Manual background T6

DXM2 PCB

JW3-LT1 jumper should be clipped

for low temperature operation

24

Page 24
Image 24
Heat Controller HEV/H manual Electrical - Low Voltage Wiring, DXM2 PCB, Hev/H Series, Low Voltage Field Wiring