FUNCTIONAL TROUBLESHOOTING

Installation, Operation & Maintenance

 

HEV/H SERIES

Heat Controller, Inc.

 

 

 

 

 

 

 

 

 

 

FUNCTIONAL TROUBLESHOOTING

 

 

 

 

 

 

 

 

Fault

Htg

Clg

Possible Cause

Solution

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check Line Voltage circuit breaker and disconnect

 

 

Main Power Problems

X

X

Green status LED off

Check for line voltage between L1 and L2 on the contactor

 

 

Check for 24VAC between R and C on DXM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check primary/secondary voltage on transformer

 

 

 

 

X

Reduced or no water flow

Check pump operation or valve operation/setting

 

 

 

 

 

in cooling

Check water flow adjust to proper flow rate

 

 

 

 

 

 

 

 

 

 

 

 

X

Water t emperature out of range in

Bring water temp within design parameters

 

 

 

 

 

 

 

 

 

 

cooling

 

 

 

 

 

 

 

 

Check for dirty air filter and clean or replace

 

 

HP Fault Code 2

X

 

Reduced or no air flow

Check fan motor operation and airflow restrictions

 

 

High Pressure

 

in heating

Dirty air coil- construction dust etc.

 

 

 

 

 

 

 

 

 

 

 

Too high of external static. Check static vs blower table

 

 

 

X

 

Air t emperature out of range in

Bring return air temp within design parameters

 

 

 

 

heating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X

X

Overcharged with refrigerant

Check superheat/subcooling vs typical operating condition

 

 

 

table

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X

X

Bad HP switch

Check switch continuity and operation - Replace

 

 

 

 

 

 

 

 

 

 

X

 

Frozen water heat exchanger

Thaw heat exchanger

 

 

 

X

X

Bad HPWS Switch

Replace HPWS Switch

 

 

 

 

 

 

 

 

 

LP/LOC Fault-Code 3

X

X

Insufficient charge

 

Check for refrigerant leaks

 

 

 

 

Compressor pump down at start-

Check charge and start-up water flow

 

 

Low Pressure/Loss of Charge

X

 

 

 

 

up

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Reduced or no water flow

Check pump operation or water valve operation/setting

 

 

 

X

 

Plugged strainer or filter - clean or replace

 

 

 

 

in heating

 

 

LT1 Fault - Code 4

 

 

Check water flow adjust to proper flow rate

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Water Low Temperature

X

 

Inadequate anti-freeze level

Check antifreeze density with hydrometer

 

 

 

 

 

 

 

 

 

 

X

 

Improper low temperature setting

Clip LT1 jumper for antifreeze (10°F) use

 

 

 

 

 

(30°F vs 10°F)

 

 

 

 

 

X

 

Water t emperature out of range

 

Bring water temp within design parameters

 

 

 

X

X

Bad thermistor

Check temp and impedance correlation per chart

 

 

 

 

 

Reduced or no air flow

Check for dirty air filter and clean or replace

 

 

 

 

X

Check fan motor operation and airflow restrictions

 

 

 

 

in cooling

 

 

 

 

 

Too high of external static - check static vs blower table

 

 

 

 

 

 

 

 

 

LT2 Fault - Code 5

 

X

Air temperature out of range

Too much cold vent air - bring entering air temp within

 

 

 

design parameters

 

 

Low Air Temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X

Improper low temperature setting

Normal airside applications will require 30°F only

 

 

 

 

 

(30°F vs 10°F)

 

 

 

 

 

X

X

Bad thermistor

Check temp and impedance correlation per chart

 

 

 

X

X

Blocked drain

Check for blockage and clean drain

 

 

 

X

X

Improper trap

 

Check trap dimensions and location ahead of vent

 

 

 

 

 

 

 

Check for piping slope away from unit

 

 

Condensate Fault-Code 6

 

X

Poor drainage

Check slope of unit toward outlet

 

 

 

 

 

 

Poor venting - check vent location

 

 

High Condensate Level

 

X

Moisture on sensor

 

Check for moisture shorting to air coil

 

 

 

X

X

Plugged air filter

Replace air filter

 

 

 

X

X

Restricted return air flow

Find and eliminate rectriction - increase return duct

 

 

 

and/or grille size

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check power supply and 24VAC voltage before and during

 

 

 

 

 

 

 

operation

 

 

 

X

X

Under voltage

Check power supply wire size

 

 

Over/Under Voltage-Code 7

Check compressor starting. Need hard start kit?

 

 

 

 

 

 

 

 

 

 

 

 

Check 24VAC and unit transformer tap for correct power

 

 

(Auto Resetting)

 

 

 

 

 

 

 

 

 

 

supply voltage

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check power supply voltage and 24VAC before and during

 

 

 

X

X

Over voltage

operation.

 

 

 

Check 24VAC and unit transformer tap for correct power

 

 

 

 

 

 

 

 

 

 

 

 

 

 

supply voltage

 

 

 

 

 

 

 

 

 

Unit Performance

X

 

Heating Mode LT2>125°F

Check for poor air flow or overcharged unit

 

 

 

 

 

 

 

 

 

Sentinel-Code 8

 

X

Cooling Mode LT1>125°F OR

Check for poor water flow, or air flow

 

 

 

 

LT2< 40°F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Swapped Thermistor

X

X

LT1 and LT2 swapped

Reverse position of thermistors

 

 

Code 9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X

X

Blower does not operate

Check blower line voltage

 

 

 

 

 

 

 

Check blower low voltage wiring

 

 

 

 

 

 

 

 

 

ECM Fault - Code 10

 

 

Blower operating with incorrect

Wrong unit size selection

 

 

 

 

 

airflow

 

 

 

 

 

 

Wrong unit family selection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wrong motor size

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Incorrect blower selection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

 

42