Heat Controller HEV/H Unit Starting And Operating Conditions, Hev/H Series, Heat Controller, Inc

Models: HEV/H

1 46
Download 46 pages 32.43 Kb
Page 33
Image 33
UNIT STARTING AND OPERATING CONDITIONS

Heat Controller, Inc.

HEV/H SERIES

Installation, Operation & Maintenance

 

 

 

UNIT STARTING AND OPERATING CONDITIONS

Starting/Commissioning Conditions

Table 9b: Commissioning Limits

Commissioning Limits
HE Series

 

Cooling
Heating

 

Air Limits

 

 

 

Min. ambient air, DB

45°F [7°C]

39°F [4°C]

Rated ambient air, DB

80.6° [27°C]

68° [20°C]

Max. ambient air, DB

110° [43°C]

85° [29°C]

Min. entering air, DB/WB

50/45°F [10/7°C]

40°F [4.5°C]

Rated entering air, DB/WB

80.6/66.2°F [27/19°C]

68°F [20°C]

Max. entering air, DB/WB

110/83°F [43/28°C]

80°F [27°C]

Water Limits

 

 

 

Min. entering water

30°F [-1°C]

20°F [-6.7°C]

Normal entering water

50-110°F [10-43°C]

30-70°F [-1 to 21°C]

Max. entering water

120°F [49°C]

90°F [32°C]

Normal Water Flow

1.5 to 3.0 gpm/ton

[1.6 to 3.2 l/m per KWI

 

 

 

 

 

33

Page 33
Image 33
Heat Controller HEV/H Unit Starting And Operating Conditions, Hev/H Series, Heat Controller, Inc, b Commissioning Limits