TROUBLESHOOTING FORM

Installation, Operation & Maintenance

HEV/H SERIES

 

 

 

Heat Controller, Inc.

 

 

 

 

 

 

 

 

TROUBLESHOOTING FORM

 

 

 

 

 

HEATING CYCLE ANALYSIS -

 

 

 

PSI

 

SAT

 

 

 

 

 

AIR

 

°

F

COIL

 

 

 

 

 

Refrigerant Type :

R-410A

R22

°F

FP2: HEATING

LIQUID LINE

°FR-410A

EXPANSION

COAX

VALVE

 

°F

 

 

°F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FLASH

 

FP1

°

 

°

 

GAS LINE

 

 

 

 

F

 

 

F

 

 

 

 

 

 

 

 

 

SENSOR

 

 

 

 

PSI

 

 

 

 

 

 

 

 

PSI

 

 

 

 

 

 

 

WATER IN

 

WATER OUT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

°F

Manual background SUCTION

COMPRESSOR

Manual background DISCHARGE

HWG

°F

Manual backgroundManual background PSISAT

Look up pressure drop in I.O.M. or spec. catalog to determine flow rate.

COOLING CYCLE ANALYSIS -

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIR

 

 

 

 

 

 

 

 

 

°

 

 

 

COIL

°

 

 

 

 

 

 

 

 

 

F

 

 

 

 

F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EXPANSION

 

 

 

COAX

 

 

 

 

 

 

 

VALVE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PSISAT

°F

Manual backgroundManual background SUCTION

COMPRESSOR

DISCHARGE

HWG

°F

 

°F

 

°F

 

°F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

°

F

FP2: FLASH

OTHER SIDE

FP1: CLG

 

 

 

 

GAS LINE

OF FILTR DR

LIQ LINE

 

 

 

 

PSI

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WATER IN

°F

PSI WATER OUT

Manual background PSISAT

Look up pressure drop in I.O.M. or spec. catalog to determine flow rate.

Heat of Extraction (Absorption) or Heat of Rejection =

 

 

________ flow rate (gpm) x ________ temp.diff. (deg. F) x ________ fluid factor

= _____________

 

= Suction temperature - suction saturation temp. =

 

(Btu/hr)

Superheat

 

(deg F)

Subcooling

= Discharge saturation temp. - liquid line temp. =

 

 

(deg F)

 

 

 

Use 500 for water, 485 for antifreeze.

Note: Never connect refrigerant gauges during startup procedures. Conduct water-side analysis using P/T ports to determine water flow and temperature difference. If water-side analysis shows poor performance, refrigerant troubleshooting may be required. Connect refrigerant gauges as a last resort.