Heat Controller HEV/H manual Vertical Installation, Hev/H Series, Vertical Sound Attenuation

Models: HEV/H

1 46
Download 46 pages 32.43 Kb
Page 10
Image 10
Figure 9: Vertical Sound Attenuation

Installation, Operation & Maintenance

HEV/H SERIES

Heat Controller, Inc.

 

 

 

VERTICAL INSTALLATION

Sound Attenuation for Vertical Units

Sound attenuation is achieved by enclosing the unit within a small mechanical room or a closet. Additional measures for sound control include the following:

1.Mount the unit so that the return air inlet is 90° to the return air grille. Refer to Figure 9. Install a sound baffle as illustrated to reduce line-of sight sound transmitted through return air grilles.

2.Mount the unit on a rubber or neoprene isolation pad to minimize vibration transmission to the building structure.

Figure 9: Vertical Sound Attenuation

Jtpmbujpo!Qbe

Jotvmbufe!Tpvoe!Cbggmf

)Pqfo!Cpui!Foet!boe!Cpuupn*

Sfuvso!Bjs!Mpvwfs!ps!Hsjmmf

Condensate Piping for Vertical Units

Install condensate trap at each unit with the top of the trap positioned below the unit condensate drain connection as shown in Figure 4. Design the depth of the trap (water- seal) based upon the amount of External Static Pressure (ESP) capability of the blower (where 2 inches [51mm] of ESP capability requires 2 inches [51mm] of trap depth). As a general rule, 1 1/2 inch [38mm] trap depth is the minimum.

Each unit must be installed with its own individual trap and connection to the condensate line (main) or riser. Provide a means to flush or blow out the condensate line. DO NOT install units with a common trap and/or vent.

Always vent the condensate line when dirt or air can collect in the line or a long horizontal drain line is required. Also vent when large units are working against higher external static pressure than other units connected to the same condensate main since this may cause poor drainage for all units on the line. WHEN A VENT IS INSTALLED IN THE DRAIN LINE, IT MUST BE LOCATED AFTER THE TRAP IN THE DIRECTION OF THE CONDENSATE FLOW.

Figure 4: Vertical Condensate Drain

ರ

ರ3HU )RRW

ರ

ರ

*Some units include a painted drain connection. Using a threaded pipe or similar device to clear any excess paint accumulated inside this fitting may ease final drain line installation.

10

Page 10
Image 10
Heat Controller HEV/H manual Vertical Installation, Hev/H Series, Vertical Sound Attenuation, ರ ರ3HU RRW ರ ರ