CONNECTING THE CABLE BETWEEN INDOOR UNIT AND OUTDOOR UNIT
Connect the cable to the Indoor unit.
■Connect the cable to the indoor unit by connecting the wires to the terminals on the control board individually according to the outdoor unit connection.
(Ensure that the color of the wires of the outdoor unit and the terminal No. are the same as those of the indoor unit.)
Terminals on the indoor unit |
|
|
|
| 3(L1) | 4(L2) |
| 5 |
| ||||||
Color of Wires |
|
|
|
|
|
|
|
|
|
|
|
|
| ||
| G/Y | BROWN |
| BLUE | RED |
| |||||||||
|
|
|
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||
|
|
|
|
|
|
|
|
| |||||||
Color of Wires |
| G/Y | BROWN |
| BLUE | RED |
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| |||
Terminals on the outdoor unit | 1(L1) | 2(L2) |
|
|
|
| 3(L1) | 4(L2) |
| 5 |
|
CAUTION
The power supply cord connected to the outdoor unit should be complied with the following specifications (UL and CSA recognized one).
|
| G | AWG #12 | |
|
|
| ||
Ø8.5mm | (0.33in) | N/YL |
| |
20m | m | |||
|
| |||
|
| (0. | ||
|
| 79in) |
The connecting cable connected to the indoor and outdoor unit should be complied with the following specifications (UL and CSA recognized one).
POWER INPUT
Ø 7.5mm | (0.30in) |
AWG #20
GN/YL
20m | m |
(0. | |
79in) |
CAUTION
Wiring must be as following diagram.
Disconnect Switch (Optional)
•May be required by local codes
•Must be rated for 15 amps
Indoor
unit
61cm max (24 in max)
Main power source
Outdoor Disconnect Switch
• Must be rated for 30 amps
Outdoor
unit
61cm max (24 in max)
13