Heat Controller HMH30BS-1SINGLE-ZONE manual Soap water method, CEvacuation, DFinishing the job

Models: HMC30AS-1 HMH30BS-1SINGLE-ZONE HMH30AS-1 HMC30BS-1

1 23
Download 23 pages 57.06 Kb
Page 18
Image 18
Soap water method

Soap water method

(1)Remove the caps from the gas side and liquid side valves.

(2)Remove the service-port cap from the gas side valve.

(3)To open the gas side valve turn the valve stem counterclockwise approximately 90°, wait for about 2~3 sec, and close it.

(4)Apply a soap water or a liquid neutral detergent on the indoor unit connection or outdoor unit connections by a soft brush to check for leakage of the connecting points of the piping.

(5)If bubbles come out, the pipes have leakage.

CEvacuation

Connect the charge hose end described in the preceding steps to the vacuum pump to evacuate the tubing and indoor unit.

Confirm the "Lo" knob of the manifold valve is open. Then, run the vacuum pump.

The operation time for evacuation varies with tubing length and capacity of the pump. The following table shows the time required for evacuation.

Required time for evacuation when 30 gal/h

vacuum pump is used

If tubing length is less

if tubing length is longer

than 10m (33 ft)

than 10m (33 ft)

 

 

10 min. or more

15 min. or more

When the desired vacuum is reached, close the "Lo" knob of the manifold valve and stop the vacuum pump.

DFinishing the job

With a service valve wrench, turn the valve stem of liquid side valve counter-clockwise to fully open the valve.

Turn the valve stem of gas side valve counter-clockwise to fully open the valve.

Loosen the charge hose connected to the gas side service port slightly to release the pressure, then remove the hose.

Replace the flare nut and its bonnet on the gas side service port and fasten the flare nut securely with an adjustable wrench. This process is very important to prevent leakage from the system.

Replace the valve caps at both gas and liquid side

service valves and fasten them tight.

This completes air purging with a vacuum pump. The air conditioner is now ready to test run.

Suction Line

Evap Line

3-way valve (Close)

3-way valve (Open)

Cap

Hexagonal wrench

Indoor unit

Outdoor unit

 

Manifold valve

Pressure

Hi

gauge

Lo

 

 

 

Open

Close

Vacuum pump

18