CHARGING

CHARGING

Each outdoor unit is factory charged (nameplate charge) for the evaporator as well as a 7.5m(25ft) line set.

Any time a line set is used either shorter or longer then the nominal 7.5m(25ft) line set length the refrigerant charge has to adjusted.

Whether the line set is made shorter or longer you must adjust the charge based on how many ft of tubing are either added or removed based on 30g(0.32oz) of R-22 per meter(foot).

Capacity

Pipe Size

Standard

Max.

Max.

Additional

 

 

Length

Elevation

length

Refrigerant

(Btu/h)

Suction

Evap

m(ft)

B m(ft)

A m(ft)

g/m(oz/ft)

 

 

 

 

 

 

 

30k

5/8"

3/8"

7.5(25)

15(49)

30(98)

30(0.32)

 

 

 

 

 

 

 

Example: A 30ft line set is used

5 additional ft X 0.32 ounces per foot= add

1.6 ounces of R-22

Important:

If you are ever uncertain of the unit charge, reclaim, evacuate and weigh in the correct charge using the unit nameplate charge adjusting for line sets longer or shorter than 7.5m(25ft).