Refrigeration Load Estimate Form
(for rooms below 32ºF) Bulletin Below32-05
Estimate for: | Estimate by: | Date: |
Example: -20ºF Ice Cream Hardening Freezer
Basis for Estimate | 12 |
| 14 |
|
| 8 | |||
|
|
|
|
|
| ||||
Room Dimensions: Width | 12 | ft. x Length | 1344 | ft. x Height | |||||
Volume: (L) | 14 |
|
| 8 | x (H) |
| = | ||
|
| x (W) |
|
|
| ||||
Ambient Temp | 85 |
| ºF. (Corrected for sun load) — | Temp. |
| ft. |
105 | cu. ft. |
ºF. = |
Note: Tables can be found in Engineering Manual,
ºF. T.D.
Insulation
| Inches | Type |
Ceiling | 4 | Foamed In place Ure |
Walls | 4 | Foamed In place Ure |
Floor | 4 | Foamed In place Ure |
Product Load | — | lbs./day of— | to be reduced from entering |
| ||
(a) | ºF. | |||||
to freezing point of— | ºF. | ºF. Initial temp. drop |
|
| ||
and then reduced from freezing point to storage Temp. of | — | ºF. = (Table 7) | — | ºF. Final temp. drop. | ||
(b) | 100 | gallons of ice cream100%@ | overrun |
|
|
|
Miscellaneous |
| motors) |
|
| |
Motors (including all blower | 0.2 | |
Lights (assume 1 watt/sq.ft.) | 168 | |
No. of People | 0 |
|
HP | 60 |
|
| Ground Temp. | (Table 21) |
Watts |
|
|
1. Transmission Loads |
|
|
|
|
Ceiling: (L)14 | x12(W) | x Heat76 | Load | (Table 1) |
North Wall: (L)14 | x8(H)W) | x Heat76 | Load | (Table 1) |
South Wall: (L)14 | x8(H)W) | x Heat76 | Load | (Table 1) |
East Wall: (W)(L)12 | x8(W)(H) | x Heat76 | Load | (Table 1) |
12 | 8 | 76 |
|
|
West Wall: (W)(L) | x (H)W) | x Heat Load | (Table 1) | |
Floor: (L)14 | x12(W) | x Heat58 | Load | (Table 1) |
12768 | = |
8512 | = |
8512 | = |
7296 | = |
7296 | = |
9744 | = |
2. | Air Change Load |
|
|
|
|
| Volume: 1344 | cu. ft12. x | Factor (Table3.49 5) x | Factor (Table 6) 56287 | = |
|
|
|
|
|
|
3. | Additional Loads |
|
|
|
|
| Electrical Motors:0.2 | HP x 75000 BTU/HP/24 hr. | 15000 | = | |
| Electrical Lights:168 | Watts x 82 |
| 13776 | = |
| People Load: 0 | People— x | BTU/24 hrs. (Table 12) |
| |
| Glass Door Load:10 | Doors x 31200 BTU/Door/24 hr. | — | = |
4.Product Load: (Table 7) (Product Load Figured @ 24 hr. Pulldown*)
(a) | Spec. Heat above freezing x | ºF. | = | |||||
| Latent Heat Fusion |
| — |
| = | |||
| lbs./day x | Spec. Heat below freezing x | ºF. Intial Temp. Drop | = | ||||
| — |
| BTU/galX 2.4(Table(10 hr19). Pull down)* | — | 102000 |
| ||
(b) | 100 | gallons of ice cream/day425 x |
| = |
*For product pulldown time other than 24 hrs. figure 24 hr. load x (24/Pulldown Time)
Total Refrigeration Load (1+2+3+4+5) BTU/24 hrs. | 241191 |
Add 10% Safety Factor | 24119 |
Total with Safety/Factor BTU/24 hrs. | 265310 |
|
|
Divide by No. of Operating Hrs. (18) to obtain BTUH Cooling Requirement | 14739 |
|
|
|
| Equipment Selection |
| |
Condensing Unit |
| Unit Cooler | System Capacity | |
Qty. | Model No. | Qty. | Model No. | BTU/hr. |