Heatcraft Refrigeration Products H-ENGM0806, H-ENGM0408 for rooms below 32ºF Bulletin Below32-05

Models: H-ENGM0408 H-ENGM0806

1 44
Download 44 pages 62.93 Kb
Page 10
Image 10
(for rooms below 32ºF) Bulletin Below32-05

Refrigeration Load Estimate Form

(for rooms below 32ºF) Bulletin Below32-05

Estimate for:

Estimate by:

Date:

Example: -20ºF Ice Cream Hardening Freezer

Basis for Estimate

12

 

14

 

 

8

 

 

 

 

 

 

Room Dimensions: Width

12

ft. x Length

1344

ft. x Height

Volume: (L)

14

 

 

8

x (H)

 

=

 

 

x (W)

 

 

 

Ambient Temp

85

 

ºF. (Corrected for sun load) — Room-20

Temp.

 

ft.

105

cu. ft.

ºF. =

Note: Tables can be found in Engineering Manual, H-ENG-2

ºF. T.D.

Insulation

 

Inches

Type

Ceiling

4

Foamed In place Ure

Walls

4

Foamed In place Ure

Floor

4

Foamed In place Ure

Product Load

lbs./day of

to be reduced from entering temp.of

 

(a)

ºF.

to freezing point of

ºF. (Table7) =

ºF. Initial temp. drop

 

 

and then reduced from freezing point to storage Temp. of

ºF. = (Table 7)

ºF. Final temp. drop.

(b)

100

gallons of ice cream100%@

overrun

 

 

 

Miscellaneous

 

motors)

 

 

Motors (including all blower

0.2

Lights (assume 1 watt/sq.ft.)

168

No. of People

0

 

HP

60

 

 

Ground Temp.

(Table 21)

Watts

 

 

1. Transmission Loads

 

 

 

 

Ceiling: (L)14

x12(W)

x Heat76

Load

(Table 1)

North Wall: (L)14

x8(H)W)

x Heat76

Load

(Table 1)

South Wall: (L)14

x8(H)W)

x Heat76

Load

(Table 1)

East Wall: (W)(L)12

x8(W)(H)

x Heat76

Load

(Table 1)

12

8

76

 

 

West Wall: (W)(L)

x (H)W)

x Heat Load

(Table 1)

Floor: (L)14

x12(W)

x Heat58

Load

(Table 1)

12768

=

8512

=

8512

=

7296

=

7296

=

9744

=

2.

Air Change Load

 

 

 

 

 

Volume: 1344

cu. ft12. x

Factor (Table3.49 5) x

Factor (Table 6) 56287

=

 

 

 

 

 

 

3.

Additional Loads

 

 

 

 

 

Electrical Motors:0.2

HP x 75000 BTU/HP/24 hr.

15000

=

 

Electrical Lights:168

Watts x 82

 

13776

=

 

People Load: 0

Peoplex

BTU/24 hrs. (Table 12)

 

=

 

Glass Door Load:10

Doors x 31200 BTU/Door/24 hr.

=

4.Product Load: (Table 7) (Product Load Figured @ 24 hr. Pulldown*)

(a)

—­

lbs./dayx

Spec. Heat above freezing x

ºF. IntialTemp. Drop

=

 

—­

lbs./dayx

Latent Heat Fusion

 

 

=

 

—­

lbs./day x

Spec. Heat below freezing x

ºF. Intial Temp. Drop

=

 

 

BTU/galX 2.4(Table(10 hr19). Pull down)*

102000

 

(b)

100­

gallons of ice cream/day425 x

 

=

*For product pulldown time other than 24 hrs. figure 24 hr. load x (24/Pulldown Time)

Total Refrigeration Load (1+2+3+4+5) BTU/24 hrs.

241191

Add 10% Safety Factor

24119

Total with Safety/Factor BTU/24 hrs.

265310

 

 

Divide by No. of Operating Hrs. (18) to obtain BTUH Cooling Requirement

14739

 

 

 

 

Equipment Selection

 

Condensing Unit

 

Unit Cooler

System Capacity

Qty.

Model No.

Qty.

Model No.

BTU/hr.

2175 West Park Place Blvd. • Stone Mountain, GA 30087 • 770.465.5600 • Fax: 770.465.5990 • www.heatcraftrpd.com

10

Page 10
Image 10
Heatcraft Refrigeration Products H-ENGM0806 for rooms below 32ºF Bulletin Below32-05, Refrigeration Load Estimate Form