Heatcraft Refrigeration Products H-ENGM0408, H-ENGM0806 manual Refrigeration Load Estimate Form

Models: H-ENGM0408 H-ENGM0806

1 44
Download 44 pages 62.93 Kb
Page 7
Image 7
Refrigeration Load Estimate Form

Refrigeration Load Estimate Form

(for rooms above 32ºF) Bulletin Above32-05

Estimate for:

Estimate by:

Date:

Example: 35ºF Convenience Store Cooler With Glass Doors

Basis for Estimate

Room Dimensions: Width8

Volume: (L) 28

Ambient Temp 85

 

28

 

 

8

 

ft. x Length

 

ft. x Height

x (W)8

8

x (H)

1792

=

ºF. (Corrected for sun load) — Room35 Temp

 

ft.

50

cu. ft.

ºF. =

Note: Tables can be found in Engineering Manual, H-ENG-2

ºF. T.D.

 

 

Insulation

 

Inches

Type

Ceiling

4

Styrene

Walls

4

Styrene

Floor

6

Concrete

Product Load

2000

lbs./dayBeerof

 

 

(a)

to be reduced from entering

temp. of

85

ºF. to35

ºF.50Temp. Drop

ºF.

(b)

200

 

lbs./dayMilkof

to be reduced from entering

temp. of

40

ºF. to35

ºF. 5Temp. Drop

ºF.

Miscellaneous

Motors (including all blower motors)0.2 Lights (assume 1 watt/sq.ft.) 224 No. of people 0

HP

60Ground Temp.

(Table 21)

Watts

 

 

1. Transmission Loads

 

 

 

 

Ceiling: (L)28

x8(W)

x 72Heat Load

(Table 1)

North Wall: (L)28

x8(H)W)

x 72Heat Load

(Table 1)

South Wall: (L)28

x8(W)H)

x 72Heat Load

(Table 1)

East Wall: (W)(L)8

x8(H)W)

x 72Heat Load

(Table 1)

8

8

72

 

West Wall: (W)(L)

x

 

x Heat Load

(Table 1)

(W)H)

Floor: (L)28

 

 

x125Heat Load

(Table 1)

x8(W)

16128 =

16128 =

16128 =

4608 =

4608 =

28000 =

2. Air Change Load

13

1.86

 

43331

 

 

1792

 

 

Volume:

 

cu. ft. x

Factor (Table 4) x

Factor (Table 6)

 

=

3.Additional Loads Electrical Motors:0.2 Electrical Lights:224 People Load: 0 Glass Door Load:10

HP x 75000 BTU/HP/24 hr. Watts x 82

PeoplexBTU/24 hrs. (Table 12) Doors x 19200 BTU/Door/24 hr.

15000 =

18368 =

=

192000 =

4. Product Load: Sensible

(Product Load Figured @ 24 hr. Pulldown*)

 

(a)

2000

lbs./day x 0.92

Spec. Heat (Table507) x

ºF. Temp Drop

(b)

200

lbs./day x 0.93

Spec. Heat (Table 57) x

ºF. Temp Drop

*For product pulldown time other than 24 hrs. figure 24 hr. load x (24/Pulldown Time)

92000 =

930 =

5. Product Load: Respiration*

 

 

 

 

 

(a)

lbs. stored x

BTU/lbs./24 hrs. (Table 8)

=

 

 

 

(b)

 

lbs. stored x

BTU/lbs./24 hrs. (Table 8)

 

=

*For consideration of previously loaded product, a multiplier of (5) is normally applied to the daily

 

product load (Line #4)

 

 

 

 

 

 

 

 

Total Refrigeration Load (1+2+3+4+5) BTU/24 hrs.

 

 

447229

 

Add 10% Safety Factor

 

 

44723

 

Total with Safety/Factor BTU/24 hrs.

 

 

491952

 

 

 

Divide by No. of Operating Hrs. (16) to obtain BTUH Cooling Requirement

 

30747

 

 

Equipment Selection

 

Condensing Unit

 

Unit Cooler

System Capacity

Qty.

Model No.

Qty.

Model No.

BTU/hr.

2175 West Park Place Blvd. • Stone Mountain, GA 30087 • 770.465.5600 • Fax: 770.465.5990 • www.heatcraftrpd.com

7

Page 7
Image 7
Heatcraft Refrigeration Products H-ENGM0408 Refrigeration Load Estimate Form, for rooms above 32ºF Bulletin Above32-05