Refrigeration Load Estimate Form

(for rooms below 32ºF) Bulletin Below32-05

Estimate for:

Estimate by:

Date:

Basis for Estimate

 

 

 

 

Room Dimensions: Width

 

ft. x Length

ft. x Height

ft.

Volume: (L)

x (W)

x (H)

=

cu. ft.

Ambient Temp

ºF. (Corrected for sun load) — Room Temp.

ºF. =

Note: Tables can be found in Engineering Manual, H-ENG-2

ºF. T.D.

 

Insulation

Inches

Type

Ceiling

Walls

Floor

Product Load

 

 

 

 

 

 

 

 

(a)

lbs./day of

 

to be reduced from entering temp. of

ºF.

to freezing point of

 

ºF. (Table 7) =

ºF. Initial temp. drop

 

and then reduced from freezing point to storage Temp. of

 

ºF. = (Table 7)

ºF. Final temp. drop.

(b)

gallons of ice cream @

overrun

 

 

 

 

 

 

 

 

 

 

 

 

 

Miscellaneous

 

 

 

 

 

 

 

 

Motors (including all blower motors)

 

HP

Ground Temp.

(Table 21)

Lights (assume 1 watt/sq.ft.)

Watts

 

 

No. of People

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1. Transmission Loads

 

 

 

 

 

 

 

 

Ceiling: (L)

x (W)

x Heat Load

 

(Table 1)

=

North Wall: (L)

x

 

 

 

x Heat Load

 

(Table 1)

=

(W)(H)

 

South Wall: (L)

x

 

 

 

x Heat Load

 

(Table 1)

=

(W)(H)

 

 

 

East Wall:

(W)(L)

 

x

(W)(H)

 

 

x Heat Load

 

(Table 1)

=

West Wall:

 

 

x

 

 

x Heat Load

 

(Table 1)

=

(W)(L)

 

(W)(H)

 

 

 

Floor: (L)

x (W)

x Heat Load

 

(Table 1)

=

 

 

 

 

 

 

 

 

 

 

 

2. Air Change Load

 

 

 

 

 

 

 

 

Volume:

cu. ft. x

Factor (Table 5) x

 

Factor (Table 6)

=

 

 

 

 

 

 

 

 

 

 

 

3. Additional Loads

 

 

 

 

 

 

 

 

Electrical Motors:

 

HP x 75000 BTU/HP/24 hr.

 

 

=

Electrical Lights:

Watts x 82

 

 

 

=

People Load:

People x

BTU/24 hrs. (Table 12)

 

=

Glass Door Load:

 

Doors x 31200 BTU/Door/24 hr.

 

=

4.Product Load: (Table 7) (Product Load Figured @ 24 hr. Pulldown*)

(a)

lbs./day x

Spec. Heat above freezing x

ºF. Intial Temp. Drop

=

 

lbs./day x

Latent Heat Fusion

 

=

 

lbs./day x

Spec. Heat below freezing x

ºF. Intial Temp. Drop

=

(b)

gallons of ice cream/day x

BTU/gal (Table 19)

 

=

*For product pulldown time other than 24 hrs. figure 24 hr. load x (24/Pulldown Time)

 

 

 

 

 

 

 

 

Total Refrigeration Load (1+2+3+4+5) BTU/24 hrs.

Add 10% Safety Factor

Total with Safety/Factor BTU/24 hrs.

Divide by No. of Operating Hrs. (18) to obtain BTUH Cooling Requirement

 

 

Equipment Selection

 

Condensing Unit

 

Unit Cooler

System Capacity

Qty.

Model No.

Qty.

Model No.

BTU/hr.