Heatcraft Refrigeration Products H-ENGM0408, H-ENGM0806 manual Example -10ºFBeef Freezer

Models: H-ENGM0408 H-ENGM0806

1 44
Download 44 pages 62.93 Kb
Page 11
Image 11
Example: -10ºF Beef Freezer

Refrigeration Load Estimate Form

(for rooms below 32ºF) Bulletin Below32-05

Estimate for:

Estimate by:

Date:

Example: -10ºF Beef Freezer

Basis for Estimate

Room Dimensions: Width

20

Volume: (L) 24

Ambient Temp 90

 

24

12

 

ft.

 

ft. x Length

ft. x Height

x (W)20

12x (H)

5760

=

 

cu. ft.

ºF. (Corrected for sun load) — Room-10

Temp.

100

ºF. =

Note: Tables can be found in Engineering Manual, H-ENG-2

ºF. T.D.

 

 

Insulation

 

Inches

Type

Ceiling

4

Foamed In place Ure

Walls

4

Foamed In place Ure

Floor

4

Foamed In place Ure

Product Load

 

 

 

 

 

(a)

3000

lbs./dayBeefof

to be reduced from entering temp35. of

ºF.

to freezing point of28

ºF. (Table7 7) =

ºF. Initial temp. drop

 

 

and then reduced from freezing point to storage Temp. of

-10

ºF. = (Table 7)

38

ºF. Final temp. drop.

(b)

gallons of ice cream@

overrun

 

 

 

Miscellaneous

Motors (including all blower motors)0.5 Lights (assume 1 watt/sq.ft.) 480 No. of People 0

HP

60

 

 

Ground Temp.

(Table 21)

Watts

 

 

1. Transmission Loads

 

 

 

 

 

 

Ceiling: (L)24

x20(W)

x Heat72

Load

(Table 1)

34560

=

North Wall: (L)24

x12(W)(H)

x Heat72

Load

(Table 1)

20736

=

24

12

72

 

 

20736

 

South Wall: (L)

x (W)(H)

x Heat Load

(Table 1)

17280

=

East Wall: (L)20

x12(H)W)

x Heat72

Load

(Table 1)

=

(W)

12

72

 

 

17280

 

20

 

 

 

West Wall: (W)(L)

x (W)(H)

x Heat Load

(Table 1)

24000

=

24

20

50

 

 

 

Floor: (L)

x (W)

x Heat Load

(Table 1)

 

=

2. Air Change Load

 

 

 

 

 

 

Volume:5760

cu. 5ft..2x

Factor 3(Table.56 5) x

Factor (Table 6) 106629

=

3.Additional Loads Electrical Motors:0.5 Electrical Lights:480 People Load: 0 Glass Door Load:0

HP x 75000 BTU/HP/24 hr. Watts x 82

PeoplexBTU/24 hrs. (Table 12) Doors x 31200 BTU/Door/24 hr.

37500 =

39360 =

=

=

4. Product Load: (Table 7) (Product Load Figured @ 24 hr. Pulldown*)

ºF. Intial16170Temp. Drop

 

(a)

3000

lbs./day0.x77

Spec. Heat above 7freezing x

=

 

3000

lbs./day100x

Latent Heat Fusion

300000

=

 

3000

lbs./day0x.4

Spec. Heat below38freezing x

ºF. Intial45600Temp. Drop

=

(b)

gallons of ice cream/dayx

BTU/galX 2.4(Table(10 hr19). Pull down)*

=

*For product pulldown time other than 24 hrs. figure 24 hr. load x (24/Pulldown Time)

 

 

 

 

 

 

Total Refrigeration Load (1+2+3+4+5) BTU/24 hrs.

 

 

679851

 

Add 10% Safety Factor

 

 

67985

 

Total with Safety/Factor BTU/24 hrs.

 

 

747836

 

 

 

Divide by No. of Operating Hrs. (18) to obtain BTUH Cooling Requirement

 

41546

 

 

 

 

 

 

 

Equipment Selection

 

Condensing Unit

 

Unit Cooler

System Capacity

Qty.

Model No.

Qty.

Model No.

BTU/hr.

2175 West Park Place Blvd. • Stone Mountain, GA 30087 • 770.465.5600 • Fax: 770.465.5990 • www.heatcraftrpd.com

11

Page 11
Image 11