Table 4
Average air changes per 24 hours for storage rooms above 32ºF. (0ºC.) due to door openings and infiltration.
| Air |
| Air |
| Air |
Volume | Changes | Volume | Changes | Volume | Changes |
Cu. Ft. | Per 24hrs. | Cu. Ft. | Per 24hrs. | Cu. Ft. | Per 24hrs. |
200 | 44.0 | 2,000 | 12.0 | 25,000 | 3.0 |
|
|
|
|
|
|
250 | 38.0 | 3,000 | 9.5 | 30,000 | 2.7 |
300 | 34.5 | 4,000 | 8.2 | 40,000 | 2.3 |
400 | 29.5 | 5,000 | 7.2 | 50,000 | 2.0 |
500 | 26.0 | 6,000 | 6.5 | 75,000 | 1.6 |
600 | 23.0 | 8,000 | 5.5 | 100,000 | 1.4 |
800 | 20.0 | 10,000 | 4.9 | 150,000 | 1.2 |
1,000 | 17.5 | 15,000 | 3.9 | 200,000 | 1.1 |
1,500 | 14.0 | 20,000 | 3.5 | 300,000 | 1.0 |
Table 5
Average air changes per 24 hours for storage rooms below 32ºF. (0ºC.) due to door openings and infiltration.
| Air |
| Air |
| Air |
Volume | Changes | Volume | Changes | Volume | Changes |
Cu. Ft. | Per 24hrs. | Cu. Ft. | Per 24hrs. | Cu. Ft. | Per 24hrs. |
200 | 33.5 | 2,000 | 9.3 | 25,000 | 2.3 |
|
|
|
|
|
|
250 | 29.0 | 3,000 | 7.4 | 30,000 | 2.1 |
300 | 26.2 | 4,000 | 6.3 | 40,000 | 1.8 |
400 | 22.5 | 5,000 | 5.6 | 50,000 | 1.6 |
500 | 20.0 | 6,000 | 5.0 | 75,000 | 1.3 |
600 | 18.0 | 8,000 | 4.3 | 100,000 | 1.1 |
800 | 15.3 | 10,000 | 3.8 | 150,000 | 1.0 |
1,000 | 13.5 | 15,000 | 3.0 | 200,000 | 0.9 |
1,500 | 11.0 | 20,000 | 2.6 | 300,000 | 0.85 |
Note: For heavy usage multiply the above values by 2.0
For long storage multiply the above values by 0.6
Table 6
Heat removed in cooling air storage room conditions (BTU per Cu. Ft.)
Storage |
|
|
|
|
|
| Temperature of Outside Air |
|
|
|
| |||||
| Room | 40ºF. (4.4ºC.) | 50ºF. (10ºC.) | 85ºF. (29.4ºC.) |
| 90ºF. (32.2ºC.) |
| 95ºF. (35ºC.) | 100ºF. (37.8ºC.) | |||||||
| Temp. |
|
|
|
|
| Relative | Humidity of Outside | Air, % |
|
|
| ||||
ºF. |
| ºC. | 70 | 80 | 70 | 80 | 50 | 60 |
| 50 | 60 |
| 50 | 60 | 50 | 60 |
55 |
| 12.8 | – | – | – | – | 1.12 | 1.34 |
| 1.41 | 1.66 |
| 1.72 | 2.01 | 2.06 | 2.44 |
50 |
| 10.0 | – | – | – | – | 1.32 | 1.54 |
| 1.62 | 1.87 |
| 1.93 | 2.22 | 2.28 | 2.65 |
45 |
| 7.2 | – | – | – | – | 1.50 | 1.73 |
| 1.80 | 2.06 |
| 2.12 | 2.42 | 2.47 | 2.85 |
40 |
| 4.4 | – | – | – | – | 1.69 | 1.92 |
| 2.00 | 2.26 |
| 2.31 | 2.62 | 2.67 | 3.65 |
35 |
| 1.7 | – | – | 0.36 | 0.41 | 1.86 | 2.09 |
| 2.17 | 2.43 |
| 2.49 | 2.79 | 2.85 | 3.24 |
30 |
| 0.24 | 0.29 | 0.58 | 0.66 | 2.00 | 2.24 |
| 2.26 | 2.53 |
| 2.64 | 2.94 | 2.95 | 3.35 | |
25 |
| 0.41 | 0.45 | 0.75 | 0.83 | 2.09 | 2.42 |
| 2.44 | 2.71 |
| 2.79 | 3.16 | 3.14 | 3.54 | |
20 |
| 0.56 | 0.61 | 0.91 | 0.99 | 2.27 | 2.61 |
| 2.62 | 2.90 |
| 2.97 | 3.35 | 3.33 | 3.73 | |
15 |
| 0.71 | 0.75 | 1.06 | 1.14 | 2.45 | 2.74 |
| 2.80 | 3.07 |
| 3.16 | 3.54 | 3.51 | 3.92 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
10 |
| 0.85 | 0.89 | 1.19 | 1.27 | 2.57 | 2.87 |
| 2.93 | 3.20 |
| 3.29 | 3.66 | 3.64 | 4.04 | |
5 |
| 0.98 | 1.03 | 1.34 | 1.42 | 2.76 | 3.07 |
| 3.12 | 3.40 |
| 3.48 | 3.87 | 3.84 | 4.27 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
0 |
| 1.12 | 1.17 | 1.48 | 1.56 | 2.92 | 3.23 |
| 3.28 | 3.56 |
| 3.64 | 4.03 | 4.01 | 4.43 | |
| 1.23 | 1.28 | 1.59 | 1.67 | 3.04 | 3.36 |
| 3.41 | 3.69 |
| 3.78 | 4.18 | 4.15 | 4.57 | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 1.35 | 1.41 | 1.73 | 1.81 | 3.19 | 3.49 |
| 3.56 | 3.85 |
| 3.93 | 4.33 | 4.31 | 4.74 | ||
| 1.50 | 1.53 | 1.85 | 1.92 | 3.29 | 3.60 |
| 3.67 | 3.96 |
| 4.05 | 4.46 | 4.42 | 4.86 | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 1.63 | 1.68 | 2.01 | 2.00 | 3.49 | 3.72 |
| 3.88 | 4.18 |
| 4.27 | 4.69 | 4.66 | 5.10 | ||
| 1.77 | 1.80 | 2.12 | 2.21 | 3.61 | 3.84 |
| 4.00 | 4.30 |
| 4.39 | 4.80 | 4.78 | 5.21 | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 1.90 | 1.95 | 2.29 | 2.38 | 3.86 | 4.05 |
| 4.21 | 4.51 |
| 4.56 | 5.00 | 4.90 | 5.44 | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Table 3, 4 & 5 extracted and reprinted by permission from ASHRAE 1972 Handbook of Fundamentals.
Table 6 extracted and reprinted by permission from ASHRAE 1967 Handbook of Fundamentals.