Coil Perfromance- Heat Reclaim MBH/SQ FT

Coil Perfromance- Heat Reclaim MBH/SQ FT

Table 14

Heat Reclaim Coil Selection Example:

Select reclaim coil for Size 26 air handler at 13280 CFM, 344 MBH reclaimed at 45°F. Temperature Difference.

A.Change the application’s requirement at application’s TD to adjusted requirement at 50°F. TD. Use Table 15:

344/0.9 = 382.2 MBH (adjusted)

B.Divide the adjusted MBH by the coil face area:

382.2/ 26.56 = 14.4 MBH (adjusted) per square foot

C.Find the coil air speed:

13280 / 26.56 = 500 fpm

D.Select coil rows and fins per inch from Table 16 at coil air

speed and with enough MBH to meet the MBH (adjusted to 50°F. TD) per square foot

Air Handler

Type A Large

Type 5 Large

Unit

Coil Face Area

Coil Face Area

Size

Square Feet

Square Feet

03

3.13

3.00

06

5.76

5.69

08

7.81

7.50

10

9.77

9.38

 

 

 

12

12.40

11.69

14

14.58

13.75

 

 

 

18

17.71

17.50

20

20.05

19.25

 

 

 

26

26.56

25.50

34

33.65

34.00

 

 

 

41

40.73

40.38

50

50.63

49.50

 

 

 

65

64.58

64.58

75

75.35

74.92

 

 

 

figured in step B:

Select 3 row 8 fin per inch coil with capacity of 14.56 MBH per square foot at 50°F. TD.

For this application, capacity equals: (14.56 x 26.56 x 0.9) or 348 MBH for size 26 at 45°F. TD.

E.When ordering, please specify refrigerant type and the total heat of rejection for each reclaim circuit. Or specify the per cent of the total heat of rejection that is reclaimed for each circuit.

Table 15 Heat reclaim correction factor for temperature difference between air and refrigerant.

Temperature Difference

20

25

30

35

40

45

50

Correction Factor

0.4

0.5

0.6

0.7

0.8

0.9

1.0

60

1.2

Table 16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refrigeration Gas

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat Reclaim

1/2" and 5/8" tube, 50°F TD, entering air to condensing temperatire

 

 

 

 

 

 

 

 

 

 

 

Type A and Type 5, hot gas reclaim, heating capacities

 

 

 

 

 

 

 

 

 

MBH per SQ FT of coil face area

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FPM, Type A Coils (1/2" DIA.)

 

 

FPM, Type 5 Coils (5/8" DIA.)

 

 

Rows

FPI

400

450

 

500

550

600

400

 

450

 

500

550

 

600

 

 

6

7.70

8.18

 

9.43

9.90

10.25

9.25

 

9.85

 

10.41

10.91

 

11.41

 

 

8

8.90

9.45

 

10.90

11.38

11.85

10.04

 

10.70

 

11.33

11.92

 

12.47

 

2

10

10.40

11.05

 

12.15

12.73

13.18

11.12

 

11.93

 

12.68

13.37

 

14.03

 

 

12

11.70

12.45

 

13.13

13.77

14.35

12.20

 

13.13

 

13.99

14.80

 

15.56

 

 

14

12.88

13.73

 

14.48

15.18

15.83

13.23

 

14.28

 

15.26

16.18

 

17.04

 

 

6

11.08

11.96

 

12.88

13.50

13.98

12.27

 

13.13

 

13.98

14.77

 

15.52

 

 

8

12.60

13.60

 

14.56

15.25

15.90

13.17

 

14.13

 

15.07

15.96

 

16.79

 

3

10

13.93

14.95

 

15.93

16.80

17.63

14.30

 

15.48

 

16.58

17.61

 

18.58

 

 

12

14.91

16.02

 

17.08

18.03

18.95

15.40

 

16.73

 

17.98

19.16

 

20.28

 

 

14

16.08

17.30

 

18.50

19.55

20.58

16.39

 

17.87

 

19.28

20.60

 

21.86

 

 

6

13.27

14.35

 

15.53

16.38

17.18

14.50

 

15.66

 

16.77

17.81

 

18.79

 

 

8

14.98

16.21

 

17.43

18.47

19.47

15.39

 

16.66

 

17.89

19.04

 

20.12

 

4

10

16.20

17.48

 

18.75

19.92

21.07

16.50

 

17.96

 

19.36

20.68

 

21.94

 

 

12

17.47

18.73

 

19.98

21.25

22.50

17.48

 

19.11

 

20.68

22.17

 

23.58

 

 

14

18.57

19.95

 

21.30

22.65

23.97

18.32

 

20.11

 

21.83

23.48

 

25.05

 

 

6

16.41

17.83

 

19.58

20.78

21.90

17.38

 

19.10

 

20.62

22.09

 

23.49

 

 

8

18.35

19.93

 

21.50

23.10

24.67

18.10

 

19.96

 

21.61

23.21

 

24.74

 

6

10

19.13

20.90

 

22.63

24.20

25.75

18.96

 

21.00

 

22.83

24.62

 

26.33

 

 

12

19.80

21.70

 

23.58

25.23

26.87

19.65

 

21.83

 

23.82

25.78

 

27.67

 

 

14

19.87

22.01

 

24.02

26.02

27.95

20.18

 

22.48

 

24.61

26.72

 

28.75

 

 

6

18.25

20.08

 

21.75

23.45

25.08

18.93

 

21.51

 

23.02

24.69

 

26.42

 

 

8

19.29

21.31

 

23.16

25.04

26.86

19.49

 

21.82

 

23.82

25.60

 

27.47

 

8

10

20.04

22.23

 

24.24

26.30

28.28

20.11

 

22.57

 

24.74

26.67

 

28.71

 

 

12

20.51

22.82

 

24.95

27.14

29.26

20.58

 

23.12

 

25.43

27.63

 

29.68

 

 

14

20.82

23.22

 

25.44

27.72

29.95

20.91

 

23.51

 

25.93

28.25

 

30.45

This table for R-22, for R404A & R507, multiply MBH by 0.98

For heat reclaim capacities at other temperature differences, multiply by factor in Table 15.

20

Page 20
Image 20
Heatcraft Refrigeration Products HCS manual Coil Perfromance- Heat Reclaim MBH/SQ FT, MBH per SQ FT of coil face area, Rows