Heatcraft Refrigeration Products HCS manual Coil Performance- Heating, Water & Steam

Models: HCS

1 44
Download 44 pages 14.9 Kb
Page 23
Image 23
Coil Performance- Heating, Water & Steam

 

Coil Performance- Heating, Water & Steam

 

 

Table 21

1/2" and 5/8" tube, entering air 60°F. DB

Hot Water

Type A and Type 5, 190°F. average water temperature^, heating capacities

 

MBH per SQ FT of coil face area (water velocity=3 fps).

 

 

 

FPM, Type A Coils (1/2" DIA.)

 

FPM, Type 5 Coils (5/8" DIA.)

 

 

Rows

FPI

400

500

600

650

 

700

400

500

600

650

700

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

11.2

12.7

14.0

14.6

 

15.2

15.1

17.0

18.5

19.3

20.0

 

 

8

14.2

16.0

17.6

18.3

 

19.0

18.8

20.9

22.8

23.7

24.5

1

10

17.1

19.2

21.0

21.9

 

22.7

21.9

24.4

26.6

27.5

28.4

 

 

12

19.9

22.3

24.4

25.3

 

26.2

24.6

27.4

29.9

30.9

31.9

 

 

14

22.7

25.4

27.6

28.6

 

29.6

26.9

30.1

32.7

33.8

34.9

 

 

6

20.3

23.3

25.9

27.1

 

28.3

25.8

29.5

32.6

34.0

35.4

 

 

8

25.0

28.6

31.8

33.3

 

34.7

30.8

35.0

38.8

40.4

42.1

2

10

29.4

33.6

37.3

39.0

 

40.6

34.7

39.6

43.9

45.8

47.6

 

 

12

33.5

38.3

42.5

44.4

 

46.2

37.8

43.4

48.1

50.3

52.3

 

 

14

37.3

42.6

47.3

49.4

 

51.4

40.4

46.5

51.7

54.2

56.3

 

 

6

27.8

32.1

36.0

37.8

 

39.6

35.2

40.8

45.6

47.9

50.1

 

 

8

33.5

38.8

43.5

45.7

 

47.8

40.1

46.9

52.9

55.7

58.3

3

10

38.4

44.7

50.2

52.7

 

55.2

43.9

51.6

58.6

61.7

64.8

 

 

12

42.8

49.9

56.3

59.2

 

61.9

46.7

55.3

63.0

66.5

70.0

 

 

14

46.7

54.7

61.8

65.0

 

68.1

48.9

58.2

66.5

70.4

74.1

To estimate for other entering air and average water temperatures, multiply by correction factor in Table 23.

Actual capacity will vary with coil circuiting and flow rate

 

 

 

 

 

5/8" and 1" tube, entering air 0°F. DB

 

 

 

 

Table 22

Type 5*** and Type 8, 190°F. steam at 5 PSIG, heating capacities

 

 

 

 

 

 

 

MBH per SQ FT of coil face area

 

 

 

 

Steam

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FPM, Type 5 Coils (5/8" DIA.)

 

 

 

FPM, Type 8 Coils (1" DIA.)

 

Rows

FPI

 

400

 

500

 

 

600

 

650

 

700

400

 

500

600

650

700

 

6

 

27.4

 

31.0

 

 

34.0

 

35.4

 

36.6

23.7

 

26.7

29.2

30.4

31.5

 

8

 

34.3

 

38.2

 

 

41.2

 

42.4

 

43.5

30.3

 

34.0

37.1

38.4

39.7

1

10

 

39.6

 

43.2

 

 

45.5

 

46.2

 

46.7

36.2

 

40.3

43.7

45.1

46.4

 

12

 

43.3

 

46.1

 

 

47.0

 

56.6

 

57.9

42.3

 

46.3

49.2

50.4

51.4

 

14

 

45.6

 

47.0

 

 

58.7

 

59.9

 

60.8

46.3

 

50.2

52.9

53.9

54.8

 

6

 

49.4

 

56.6

 

 

62.8

 

65.6

 

68.3

 

 

 

 

 

 

 

 

8

 

56.9

 

65.4

 

 

72.6

 

75.7

 

78.4

 

 

 

 

 

 

 

2

10

 

62.8

 

72.3

 

 

79.7

 

82.7

 

85.3

 

 

 

 

 

 

 

 

12

 

67.5

 

77.5

 

 

84.8

 

87.5

 

89.8

 

 

 

 

 

 

 

 

14

 

71.3

 

81.4

 

 

88.3

 

90.7

 

92.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Type 8 coils offered as one row only on model 65 and 75.

Note: Please contact your representative for ARI ratings for coils. These tables are only estimates. To estimate for other entering air and steam pressures multiply by correction factor in Table 23.

Table 23

Capacity connections Factors to Table 21 for other than 60°F. and 190 average water temperature^

Capcity Correction Facors to Table 22 for other than 0°F. air and 5 PSIG steam***.

Ent Air

 

Average Water Temperature^,

°F.

 

 

 

Steam Pressure, PSIG

 

 

Temp. °F.

120

130

140

150

160

170

180

190

5

10

20

25

30

40

50

-20

1.077

1.154

1.231

1.308

1.385

1.462

1.538

1.615

1.088

1.142

1.228

1.263

1.295

1.351

1.395

-10

1.000

1.077

1.154

1.231

1.308

1.385

1.462

1.538

1.044

1.098

1.184

1.219

1.251

1.306

1.351

0

0.923

1.000

1.077

1.154

1.231

1.308

1.385

1.462

1.000

1.054

1.140

1.175

1.207

1.262

1.306

10

0.846

0.923

1.000

1.077

1.154

1.231

1.308

1.385

0.956

1.010

1.096

1.131

1.162

1.218

1.262

20

0.769

0.846

0.923

1.000

1.077

1.154

1.231

1.308

0.912

0.966

1.052

1.087

1.118

1.174

1.218

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30

0.692

0.769

0.846

0.923

1.000

1.077

1.154

1.231

0.868

0.922

1.007

1.043

1.074

1.130

1.174

40

0.615

0.692

0.769

0.846

0.923

1.000

1.077

1.154

0.824

0.878

0.963

0.999

1.030

1.086

1.130

50

0.538

0.615

0.692

0.769

0.846

0.923

1.000

1.077

0.780

0.834

0.919

0.955

0.986

1.042

1.086

60

0.462

0.538

0.615

0.692

0.769

0.846

0.923

1.000

0.736

0.790

0.875

0.911

0.942

0.998

1.042

70

0.385

0.462

0.538

0.615

0.692

0.769

0.846

0.923

0.692

0.746

0.831

0.867

0.898

0.954

0.998

80

0.308

0.385

0.462

0.538

0.615

0.692

0.769

0.846

0.648

0.702

0.787

0.823

0.854

0.910

0.954

90

0.231

0.308

0.385

0.462

0.538

0.615

0.692

0.769

0.604

0.658

0.743

0.779

0.810

0.866

0.910

100

0.154

0.231

0.308

0.385

0.462

0.538

0.615

0.692

0.560

0.614

0.699

0.734

0.766

0.822

0.866

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

^ Average water temperature = (entering water temp + leaving water temp) divided by 2.

**For type 5, at 5 PSIG, if (total MBH divided by 0.961) divided by coil tubes is more than to 50 LB per tube, the condensate loading may be too high. At higher pressures the condensate loading can be more than 50 LB per tube. Get a computer rating for the application.

23

Page 23
Image 23
Heatcraft Refrigeration Products HCS manual Coil Performance- Heating, Water & Steam