Heatcraft Refrigeration Products HCS manual Air Pressure Drops- Cabinets, Filters, Wet Coils

Models: HCS

1 44
Download 44 pages 14.9 Kb
Page 41
Image 41
Air Pressure Drops- Cabinets, Filters, Wet Coils

Air Pressure Drops- Cabinets, Filters, Wet Coils Manual backgroundManual background

Cabinet And Filter Air Pressure Drop

 

Air Pressure Drop - inches of water

 

 

Air Velocity^ - Feet per minute

 

 

 

 

 

Component

 

200

250

300

350

400

 

450

500

550

600

Cabinet:

V Style Cabinet^^

 

.10

.13

 

.16

.20

.24

.29

 

Economizer Section^^

 

.02

.03

.03

 

.04

.05

.06

.07

Filters:

Throwaway

2" Depth

.05

.08

.11

.15

.19

 

.24

.28

——

——

flat & hi

35% Efficient , Pleated

2" Depth

.08

.10

.13

.16

.21

 

.25

.30

.37

——

capacity

Permanent, Aluminum, Cleanable

2" Depth

.03

.04

.06

.08

.10

 

.13

.15

.18

.21

flat, 4"

35% Efficient , Pleated

4" Depth

.06

.07

.10

.13

.17

 

.20

.25

.29

.34

 

(60 - 65%) Efficient

21" Depth

.12

.16

.21

.26

.32

 

.38

.45

Filters:

Bag Filter

30" Depth

.19

.24

.28

 

.33

.37

.41

.44

 

 

37" Depth

.12

.17

.23

 

.27

.33

.37

.41

Medium

(80 - 85%) Efficient

21" Depth

.14

.20

.26

.32

.38

 

.44

.51

 

Bag Filter

30" Depth

.23

.28

.34

 

.40

.47

.51

.55

 

 

37" Depth

.15

.21

.26

 

.32

.38

.45

.52

and

(90 - 95%) Efficient

21" Depth

.20

.28

.36

.44

.52

 

.61

.70

 

Bag Filter

30" Depth

.32

.39

.46

 

.53

.60

.66

.72

 

 

37" Depth

.22

.29

.36

 

.44

.54

.60

.68

High

(60 - 65%) Cartridge Filter

6" Depth

.15

.20

.26

.33

 

 

 

12" Depth

.22

.28

.34

 

.41

.50

.58

.68

 

(80 - 85%) Cartridge Filter

6" Depth

.22

.29

.37

.46

 

Efficiency

 

12" Depth

.26

.32

.38

 

.46

.55

.64

.74

 

(90 - 95%) Cartridge Filter

6" Depth

.25

.34

.44

.56

 

 

 

12" Depth

.29

.35

.42

 

.50

.59

.70

.82

The filter air pressure drop is for air through clean filters.

Type A (1/2" O.D.) Wet Coil Air Pressure Drop*

 

Type 5 (5/8" O.D.) Wet Coil Air Pressure Drop*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rows

Fin

Air Velocity - Feet

per minute^

 

 

Rows

Fin

Air Velocity - Feet

per minute^

 

 

Series

400

450

500

 

550

600

650

 

 

Series

400

450

500

 

550

600

650

 

6

0.18

0.22

0.26

 

0.30

0.34

0.39

 

 

6

0.25

0.30

0.36

 

0.42

0.49

0.56

 

8

0.22

0.27

0.32

 

0.37

0.42

0.48

 

 

8

0.31

0.37

0.44

 

0.52

0.60

0.68

3

10

0.26

0.32

0.37

 

0.43

0.50

0.56

 

3

10

0.36

0.44

0.52

 

0.58

0.67

0.79

 

12

0.30

0.37

0.43

 

0.50

0.57

0.65

 

 

12

0.42

0.50

0.59

 

0.66

0.76

0.87

 

14

0.34

0.41

0.49

 

0.56

0.64

0.73

 

 

14

0.45

0.54

0.64

 

0.74

0.85

0.97

 

6

0.24

0.29

0.35

 

0.40

0.47

0.53

 

 

6

0.33

0.40

0.48

 

0.56

0.65

0.74

 

8

0.30

0.36

0.43

 

0.50

0.57

0.65

 

 

8

0.41

0.50

0.59

 

0.69

0.80

0.91

4

10

0.35

0.43

0.51

 

0.59

0.67

0.77

 

4

10

0.48

0.58

0.69

 

0.81

0.93

1.06

 

12

0.41

0.49

0.58

 

0.68

0.77

0.88

 

 

12

0.56

0.67

0.79

 

0.92

1.02

1.20

 

14

0.46

0.56

0.66

 

0.76

0.87

0.99

 

 

14

0.63

0.75

0.89

 

1.03

1.14

1.34

 

6

0.31

0.38

0.45

 

0.53

0.61

0.70

 

 

6

0.41

0.50

0.60

 

0.70

0.81

0.93

 

8

0.39

0.47

0.56

 

0.65

0.74

0.84

 

 

8

0.51

0.62

0.74

 

0.86

0.99

1.13

5

10

0.46

0.55

0.65

 

0.75

0.86

0.97

 

5

10

0.60

0.73

0.87

 

1.01

1.12

1.32

 

12

0.53

0.63

0.74

 

0.85

0.97

1.10

 

 

12

0.69

0.84

0.99

 

1.11

1.27

1.50

 

14

0.59

0.71

0.83

 

0.95

1.09

1.22

 

 

14

0.78

0.94

1.11

 

1.24

1.42

1.68

 

6

0.37

0.46

0.54

 

0.64

0.74

0.84

 

 

6

0.49

0.60

0.72

 

.84

0.98

1.12

 

8

0.46

0.56

0.67

 

0.78

0.90

1.03

 

 

8

0.61

0.74

0.88

 

1.03

1.19

1.36

6

10

0.55

0.67

0.79

 

0.92

1.05

1.18

 

6

10

0.72

0.88

1.04

 

1.21

1.40

1.59

 

12

0.63

0.77

0.90

 

1.04

1.19

1.34

 

 

12

0.83

1.01

1.19

 

1.38

1.59

1.80

 

14

0.72

0.86

1.01

 

1.17

1.33

1.49

 

 

14

0.94

1.13

1.33

 

1.55

1.77

2.01

 

6

0.51

0.62

0.74

 

0.87

0.99

1.12

 

 

6

0.66

0.80

0.96

 

1.12

1.30

1.49

 

8

0.63

0.77

0.90

 

1.05

1.20

1.35

 

 

8

0.82

0.99

1.18

 

1.38

1.59

1.82

8

10

0.75

0.90

1.06

 

1.23

1.40

1.58

 

8

10

0.97

1.17

1.39

 

1.62

1.86

2.12

 

12

0.86

1.03

1.21

 

1.40

1.59

1.79

 

 

12

1.11

1.34

1.58

 

1.84

2.12

2.41

 

14

0.96

1.15

1.35

 

1.56

1.78

2.01

 

 

14

1.25

1.51

1.78

 

2.06

2.36

2.68

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Wet coil air pressure drop for air entering at 80 °F DB and 67 °F WB over rippled high efficiency fins. Inches of water. ^ Air velocity = CFM divided by coil or filter face area in square feet. See table at top of page 40.

^^ Use face area of large coil to calculate air speed through AHV cabinet and economizer section.

41

Page 41
Image 41
Heatcraft Refrigeration Products HCS manual Air Pressure Drops- Cabinets, Filters, Wet Coils