Coil Performance- Direct Expansion MBH/SQ FT
Table 17
Wet Evaporator Capacity
1/2" and 5/8" tube, entering air 80°F. DB, 67°F. WB
Type A and Type 5, direct expansion at 40ºF. evaporating, cooling capacities
MBH per SQ FT of coil face area
|
| FPM, Type A Coils (1/2" DIA.) |
| FPM, Type 5 Coils (5/8" DIA.) |
| |||||||
Rows | FPI | 400 | 450 | 500 | 550 | 600 | 400 | 450 | 500 | 550 |
| 600 |
| 6 | 11.3 | 12.1 | 12.8 | 13.4 | 14.0 | 13.1 | 13.8 | 14.5 | 15.2 |
| 15.8 |
| 8 | 13.0 | 13.9 | 14.7 | 15.4 | 16.1 | 14.9 | 15.8 | 16.6 | 17.4 |
| 18.1 |
3 | 10 | 14.4 | 15.3 | 16.2 | 17.0 | 17.8 | 16.2 | 17.2 | 18.2 | 19.0 |
| 19.8 |
| 12 | 15.4 | 16.5 | 17.4 | 18.3 | 19.1 | 17.3 | 18.4 | 19.4 | 20.3 |
| 21.2 |
| 14 | 16.3 | 17.4 | 18.4 | 19.3 | 20.2 | 18.0 | 19.2 | 20.4 | 21.4 |
| 22.4 |
| 6 | 14.0 | 15.0 | 16.0 | 16.9 | 17.7 | 15.8 | 16.8 | 17.8 | 18.7 |
| 19.5 |
| 8 | 15.9 | 17.1 | 18.2 | 19.2 | 20.1 | 17.7 | 18.9 | 20.0 | 21.0 |
| 22.0 |
4 | 10 | 17.4 | 18.7 | 19.8 | 20.9 | 22.0 | 19.0 | 20.4 | 21.7 | 22.8 |
| 23.9 |
| 12 | 18.5 | 19.9 | 21.2 | 22.3 | 23.4 | 19.9 | 21.4 | 22.8 | 24.1 |
| 25.3 |
| 14 | 19.4 | 20.9 | 22.2 | 23.5 | 24.6 | 20.7 | 22.3 | 23.8 | 25.2 |
| 26.5 |
| 6 | 15.9 | 17.1 | 18.3 | 19.3 | 20.3 | 17.9 | 19.2 | 20.5 | 21.6 |
| 22.6 |
| 8 | 18.3 | 19.7 | 21.1 | 22.3 | 23.5 | 19.8 | 21.3 | 22.7 | 24.0 |
| 25.2 |
5 | 10 | 19.8 | 21.3 | 22.8 | 24.2 | 25.5 | 21.0 | 22.7 | 24.3 | 25.7 |
| 27.1 |
| 12 | 20.9 | 22.6 | 24.2 | 25.6 | 27.0 | 21.8 | 23.6 | 25.4 | 27.0 |
| 28.5 |
| 14 | 21.8 | 23.6 | 25.3 | 26.8 | 28.3 | 22.5 | 24.4 | 26.3 | 28.0 |
| 29.6 |
| 6 | 17.8 | 19.2 | 20.5 | 21.7 | 22.8 | 19.7 | 21.2 | 22.7 | 24.0 |
| 25.3 |
| 8 | 19.7 | 21.3 | 22.7 | 24.1 | 25.4 | 21.4 | 23.1 | 24.8 | 26.3 |
| 27.8 |
6 | 10 | 21.1 | 22.8 | 24.4 | 25.9 | 27.2 | 22.5 | 24.4 | 26.3 | 28.0 |
| 29.7 |
| 12 | 22.1 | 23.9 | 25.6 | 27.2 | 28.7 | 23.3 | 25.3 | 27.3 | 29.2 |
| 31.0 |
| 14 | 22.9 | 24.8 | 26.6 | 28.2 | 29.8 | 23.9 | 26.0 | 28.1 | 30.1 |
| 32.0 |
| 6 | 20.9 | 22.7 | 24.3 | 25.9 | 27.4 | 22.3 | 24.2 | 26.0 | 27.7 |
| 29.4 |
| 8 | 22.7 | 24.7 | 26.6 | 28.4 | 30.0 | 23.8 | 25.9 | 28.0 | 29.9 |
| 31.7 |
8 | 10 | 23.9 | 26.1 | 28.1 | 30.1 | 31.9 | 24.6 | 27.0 | 29.3 | 31.3 |
| 33.3 |
| 12 | 24.8 | 27.1 | 29.3 | 31.3 | 33.2 | 25.2 | 27.7 | 30.1 | 32.4 |
| 34.6 |
| 14 | 25.4 | 27.8 | 30.1 | 32.2 | 34.2 | 25.7 | 28.2 | 30.7 | 33.1 |
| 35.4 |
|
|
|
|
|
|
|
|
|
|
|
|
|
Note: Please contact your representative for ARI ratings for coils. These tables are only estimates. For extimates for other web bulb and evaporator temperatures, multiply by correction factors in Table 18.
Actual capacity will vary
with coil circuiting
Table 18:
|
|
|
|
|
| Capacity Correction Factors* To Coil Performance |
|
|
|
|
| |||||
|
|
|
|
|
| Of 67°F Wb And 40°F Evaporating |
|
|
|
|
|
| ||||
Ent Air WB |
|
|
|
|
| Refrigerant Evaporating Temperature °F. |
|
|
|
|
|
| ||||
Temp. °F. | 35 | 36 | 37 | 38 | 39 | 40 | 41 | 42 | 43 | 44 | 45 | 46 | 47 | 48 | 49 | 50 |
60 | 0.820 | 0.794 | 0.768 | 0.740 | 0.713 | 0.685 | 0.656 | 0.628 | 0.598 | 0.568 | 0.538 | 0.506 | 0.475 | 0.442 | 0.409 | 0.376 |
61 | 0.862 | 0.837 | 0.810 | 0.783 | 0.756 | 0.727 | 0.698 | 0.670 | 0.640 | 0.610 | 0.580 | 0.548 | 0.517 | 0.484 | 0.452 | 0.418 |
62 | 0.907 | 0.881 | 0.854 | 0.827 | 0.799 | 0.771 | 0.743 | 0.714 | 0.684 | 0.654 | 0.623 | 0.592 | 0.561 | 0.528 | 0.496 | 0.462 |
63 | 0.950 | 0.923 | 0.897 | 0.870 | 0.842 | 0.814 | 0.785 | 0.756 | 0.727 | 0.696 | 0.666 | 0.635 | 0.603 | 0.571 | 0.538 | 0.505 |
64 | 0.994 | 0.969 | 0.942 | 0.914 | 0.887 | 0.859 | 0.831 | 0.802 | 0.772 | 0.742 | 0.712 | 0.680 | 0.649 | 0.616 | 0.583 | 0.550 |
65 | 1.040 | 1.014 | 0.988 | 0.960 | 0.933 | 0.905 | 0.876 | 0.847 | 0.818 | 0.788 | 0.757 | 0.726 | 0.694 | 0.662 | 0.629 | 0.596 |
66 | 1.087 | 1.061 | 1.035 | 1.008 | 0.980 | 0.952 | 0.923 | 0.894 | 0.864 | 0.835 | 0.804 | 0.773 | 0.741 | 0.709 | 0.676 | 0.642 |
67 | 1.136 | 1.109 | 1.083 | 1.055 | 1.028 | 1.000 | 0.971 | 0.943 | 0.913 | 0.883 | 0.852 | 0.822 | 0.789 | 0.757 | 0.724 | 0.691 |
68 | 1.185 | 1.158 | 1.132 | 1.105 | 1.077 | 1.050 | 1.020 | 0.992 | 0.962 | 0.932 | 0.901 | 0.870 | 0.838 | 0.806 | 0.773 | 0.740 |
69 | 1.235 | 1.209 | 1.182 | 1.155 | 1.127 | 1.100 | 1.071 | 1.042 | 1.012 | 0.982 | 0.952 | 0.920 | 0.889 | 0.856 | 0.824 | 0.790 |
70 | 1.286 | 1.260 | 1.235 | 1.206 | 1.179 | 1.152 | 1.122 | 1.094 | 1.063 | 1.033 | 1.003 | 0.972 | 0.940 | 0.908 | 0.875 | 0.841 |
71 | 1.339 | 1.313 | 1.285 | 1.260 | 1.231 | 1.203 | 1.175 | 1.146 | 1.115 | 1.086 | 1.055 | 1.024 | 0.993 | 0.960 | 0.927 | 0.894 |
72 | 1.393 | 1.365 | 1.340 | 1.314 | 1.285 | 1.257 | 1.229 | 1.200 | 1.170 | 1.140 | 1.110 | 1.079 | 1.046 | 1.015 | 0.981 | 0.948 |
73 | 1.450 | 1.422 | 1.395 | 1.369 | 1.340 | 1.313 | 1.285 | 1.255 | 1.225 | 1.195 | 1.165 | 1.134 | 1.103 | 1.070 | 1.036 | 1.003 |
74 | 1.505 | 1.479 | 1.451 | 1.425 | 1.396 | 1.370 | 1.340 | 1.310 | 1.281 | 1.252 | 1.221 | 1.190 | 1.159 | 1.126 | 1.094 | 1.060 |
* Note: correction factor = (enthalpy of air temperature - enthalpy of evaporator temperature) in BTU/LB divided by 16.39