Heatcraft Refrigeration Products HCS manual Coil Performance- Direct Expansion MBH/SQ FT

Models: HCS

1 44
Download 44 pages 14.9 Kb
Page 21
Image 21
Coil Performance- Direct Expansion MBH/SQ FT

Coil Performance- Direct Expansion MBH/SQ FT Actual capacity will varyManual background

Table 17

Wet Evaporator Capacity

1/2" and 5/8" tube, entering air 80°F. DB, 67°F. WB

Type A and Type 5, direct expansion at 40ºF. evaporating, cooling capacities

MBH per SQ FT of coil face area

 

 

FPM, Type A Coils (1/2" DIA.)

 

FPM, Type 5 Coils (5/8" DIA.)

 

Rows

FPI

400

450

500

550

600

400

450

500

550

 

600

 

6

11.3

12.1

12.8

13.4

14.0

13.1

13.8

14.5

15.2

 

15.8

 

8

13.0

13.9

14.7

15.4

16.1

14.9

15.8

16.6

17.4

 

18.1

3

10

14.4

15.3

16.2

17.0

17.8

16.2

17.2

18.2

19.0

 

19.8

 

12

15.4

16.5

17.4

18.3

19.1

17.3

18.4

19.4

20.3

 

21.2

 

14

16.3

17.4

18.4

19.3

20.2

18.0

19.2

20.4

21.4

 

22.4

 

6

14.0

15.0

16.0

16.9

17.7

15.8

16.8

17.8

18.7

 

19.5

 

8

15.9

17.1

18.2

19.2

20.1

17.7

18.9

20.0

21.0

 

22.0

4

10

17.4

18.7

19.8

20.9

22.0

19.0

20.4

21.7

22.8

 

23.9

 

12

18.5

19.9

21.2

22.3

23.4

19.9

21.4

22.8

24.1

 

25.3

 

14

19.4

20.9

22.2

23.5

24.6

20.7

22.3

23.8

25.2

 

26.5

 

6

15.9

17.1

18.3

19.3

20.3

17.9

19.2

20.5

21.6

 

22.6

 

8

18.3

19.7

21.1

22.3

23.5

19.8

21.3

22.7

24.0

 

25.2

5

10

19.8

21.3

22.8

24.2

25.5

21.0

22.7

24.3

25.7

 

27.1

 

12

20.9

22.6

24.2

25.6

27.0

21.8

23.6

25.4

27.0

 

28.5

 

14

21.8

23.6

25.3

26.8

28.3

22.5

24.4

26.3

28.0

 

29.6

 

6

17.8

19.2

20.5

21.7

22.8

19.7

21.2

22.7

24.0

 

25.3

 

8

19.7

21.3

22.7

24.1

25.4

21.4

23.1

24.8

26.3

 

27.8

6

10

21.1

22.8

24.4

25.9

27.2

22.5

24.4

26.3

28.0

 

29.7

 

12

22.1

23.9

25.6

27.2

28.7

23.3

25.3

27.3

29.2

 

31.0

 

14

22.9

24.8

26.6

28.2

29.8

23.9

26.0

28.1

30.1

 

32.0

 

6

20.9

22.7

24.3

25.9

27.4

22.3

24.2

26.0

27.7

 

29.4

 

8

22.7

24.7

26.6

28.4

30.0

23.8

25.9

28.0

29.9

 

31.7

8

10

23.9

26.1

28.1

30.1

31.9

24.6

27.0

29.3

31.3

 

33.3

 

12

24.8

27.1

29.3

31.3

33.2

25.2

27.7

30.1

32.4

 

34.6

 

14

25.4

27.8

30.1

32.2

34.2

25.7

28.2

30.7

33.1

 

35.4

 

 

 

 

 

 

 

 

 

 

 

 

 

Note: Please contact your representative for ARI ratings for coils. These tables are only estimates. For extimates for other web bulb and evaporator temperatures, multiply by correction factors in Table 18.

Actual capacity will vary

with coil circuiting

Table 18:

 

 

 

 

 

 

Capacity Correction Factors* To Coil Performance

 

 

 

 

 

 

 

 

 

 

 

Of 67°F Wb And 40°F Evaporating

 

 

 

 

 

 

Ent Air WB

 

 

 

 

 

Refrigerant Evaporating Temperature °F.

 

 

 

 

 

 

Temp. °F.

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

60

0.820

0.794

0.768

0.740

0.713

0.685

0.656

0.628

0.598

0.568

0.538

0.506

0.475

0.442

0.409

0.376

61

0.862

0.837

0.810

0.783

0.756

0.727

0.698

0.670

0.640

0.610

0.580

0.548

0.517

0.484

0.452

0.418

62

0.907

0.881

0.854

0.827

0.799

0.771

0.743

0.714

0.684

0.654

0.623

0.592

0.561

0.528

0.496

0.462

63

0.950

0.923

0.897

0.870

0.842

0.814

0.785

0.756

0.727

0.696

0.666

0.635

0.603

0.571

0.538

0.505

64

0.994

0.969

0.942

0.914

0.887

0.859

0.831

0.802

0.772

0.742

0.712

0.680

0.649

0.616

0.583

0.550

65

1.040

1.014

0.988

0.960

0.933

0.905

0.876

0.847

0.818

0.788

0.757

0.726

0.694

0.662

0.629

0.596

66

1.087

1.061

1.035

1.008

0.980

0.952

0.923

0.894

0.864

0.835

0.804

0.773

0.741

0.709

0.676

0.642

67

1.136

1.109

1.083

1.055

1.028

1.000

0.971

0.943

0.913

0.883

0.852

0.822

0.789

0.757

0.724

0.691

68

1.185

1.158

1.132

1.105

1.077

1.050

1.020

0.992

0.962

0.932

0.901

0.870

0.838

0.806

0.773

0.740

69

1.235

1.209

1.182

1.155

1.127

1.100

1.071

1.042

1.012

0.982

0.952

0.920

0.889

0.856

0.824

0.790

70

1.286

1.260

1.235

1.206

1.179

1.152

1.122

1.094

1.063

1.033

1.003

0.972

0.940

0.908

0.875

0.841

71

1.339

1.313

1.285

1.260

1.231

1.203

1.175

1.146

1.115

1.086

1.055

1.024

0.993

0.960

0.927

0.894

72

1.393

1.365

1.340

1.314

1.285

1.257

1.229

1.200

1.170

1.140

1.110

1.079

1.046

1.015

0.981

0.948

73

1.450

1.422

1.395

1.369

1.340

1.313

1.285

1.255

1.225

1.195

1.165

1.134

1.103

1.070

1.036

1.003

74

1.505

1.479

1.451

1.425

1.396

1.370

1.340

1.310

1.281

1.252

1.221

1.190

1.159

1.126

1.094

1.060

* Note: correction factor = (enthalpy of air temperature - enthalpy of evaporator temperature) in BTU/LB divided by 16.39

21

Page 21
Image 21
Heatcraft Refrigeration Products HCS manual Coil Performance- Direct Expansion MBH/SQ FT