Air Handler Performance- Direct Expansion

Table 2

Comfort Cooling

1/2" tube, entering air at 80°F. DB and 67°F. WB** 1/2" Tube , direct expansion, cooling capacities 10 FPI**, large coils, 500 FPM**

 

CFM

Coil

 

 

MBH - 4 ROWS

 

 

 

 

 

 

MBH - 6 ROWS

 

 

 

Unit

Std

Face

35°F. SST

40°F. SST

 

45°F. SST

 

35°F. SST

 

40°F. SST

 

 

45°F. SST

 

Size

Air

Area

Total

Sens.

Total

Sens.

 

Total

 

Sens.

Total

 

Sens.

Total

 

Sens.

 

Total

 

Sens.

03

1565

3.13

70

44

58

38

 

44

 

33

87

 

53

75

 

48

 

61

 

42

06

2880

5.76

132

81

110

72

 

90

 

64

163

 

99

138

 

88

 

114

 

78

08

3905

7.81

177

110

150

99

 

123

 

88

219

 

133

189

 

119

 

154

 

105

10

4885

9.77

224

139

190

125

 

152

 

109

278

 

168

235

 

150

 

192

 

131

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

6200

12.40

284

177

241

157

 

194

 

140

353

 

214

301

 

191

 

242

 

166

14

7290

14.58

336

207

284

187

 

231

 

165

416

 

253

354

 

225

 

290

 

197

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18

8855

17.71

408

250

345

226

 

280

 

201

505^

 

308

428

 

272

 

352

 

242

20

10025

20.05

459

282

390

256

 

319

 

226

568

 

343

489

 

308

 

399

 

273

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

26

13280

26.56

614

379

520

338

 

418

 

300

762^

 

461

648^

 

411

 

524

 

358

34

16825

33.65

778^

480

659^

428

 

530^

 

380

966^

 

584

821^

 

520

 

664^

 

454

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

41

20365

40.73

942^

581

797^

518

 

641^

 

460

1168^^

 

706

994^^

 

630

 

804^

 

549

50

25313

50.63

1169^

721

992^

648

 

803^

 

577

1488*

 

875

1239*

 

788

 

1002*

 

686

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

32290

64.58

1447^

905

1253^

827

 

1035^

 

742

1820*

 

1104

1574*

 

995

 

1293*

 

884

75

37675

75.35

1689*

1056

1462*

965

 

1208*

 

866

2124*

 

1288

1836*

 

1161

 

1509*

 

1032

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 3

Comfort Cooling

5/8" tube, entering air at 80°F. DB and 67°F. WB**

5/8" Tube, direct expansion, cooling capacities

10 FPI**, large coils, 500 FPM**

 

CFM

Coil

 

 

MBH - 4 ROWS

 

 

 

 

MBH - 6 ROWS

 

 

Unit

Std

Face

35°F. SST

 

40°F. SST

45°F. SST

35°F. SST

40°F. SST

45°F. SST

Size

Air

Area

Total

Sens.

 

Total

Sens.

Total

Sens.

Total

Sens.

Total

Sens.

Total

Sens.

03

1500

3.00

75

47

 

62

42

48

37

88

54

76

49

63

43

06

2844

5.69

138

88

 

111

77

84

67

173

105

147

94

118

81

08

3750

7.50

178

114

 

157

106

129

95

228

139

192

122

152

106

10

4690

9.38

234

148

 

192

130

157

116

283

173

244

156

198

136

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

5844

11.69

296

186

 

246

165

192

144

346

212

301

192

249

169

14

6875

13.75

349

220

 

295

196

235

172

412

253

345

221

290

199

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18

8750

17.50

444

280

 

375

249

299

219

536

326

455

289

369

254

20

9625

19.25

467

297

 

408

273

335

245

591

360

500

317

412

279

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

26

12750

25.50

651

408

 

540

362

422

314

779^

475

665

421

547

371

34

17000

34.00

868^

544

 

720^

482

563

418

1039^

633

886^

562

729^

495

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

41

20188

40.38

1030^

646

 

855^

573

669

497

1234^

752

1052^

667

866^

587

50

24750

49.50

1268^

790

 

1059^

709

830^

610

1520*

923

1282^

817

1062^

722

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

32292

64.58

1651^

1032

 

1401^

933

1116^

809

1989*

1212

1692*

1067

1369^

937

75

37458

74.92

1915^

1197

 

1625^

1082

1295^

939

2307*

1405

1962*

1238

1588^

1087

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SST = Saturated Suction Temperature MBH = BTU per Hour in Thousands Sens. = Sensible Capacity

All coils have single refrigerant distributors unless noted as below:

^These selections require two circuits. ^^ These selections require three circuits. * These selections require four circuits.

**To estimate performance of coils at other than 10 FPI or at other air speeds or with other refrigerant or air temperatures see page 21, or call your representative. With your representative, you can have specific computer selected coils rated for your job conditions.

14

Page 14
Image 14
Heatcraft Refrigeration Products HCS manual Air Handler Performance- Direct Expansion, Coil