4-2. TROUBLESHOOTING
(Continued) |
|
|
Problem | Cause | Correction |
|
|
|
Slow to decrease | Condenser obstructed by dirt. | Clean the Condenser. |
in temperature (decline in |
|
|
performance) | Evaporator iced up. | Perform a |
| Refrigerating problem | Check refrigeration circuit and |
|
| components. |
|
|
|
Display temperature does | In Frigiprobe mode, the display | Normal |
not match the actual inlet air | shows the product temperature. |
|
temperature. (No alarm) | In timer mode, or hold mode, | Ohm out the probe and check |
| ||
| the probe may be showing the | the reading with the table on |
| wrong temperature. | page |
|
| it is out of tolerance. |
|
|
|
Green compressor indicator | Compressor and condenser fan |
|
light on and the compressor | do not work: |
|
not working, or working | - Faulty contactor | Check contactor and change if |
sometimes. |
| neccessary. |
| - Faulty control board | Replace control board. |
| voltage across terminals |
|
| Compressor works, but condenser |
|
| fan does not: |
|
| - Faulty condenser fan | Replace fan. |
| Compressor and condenser fan |
|
| work together: |
|
| - Faulty protection component | Check items and replace if |
| for the compressor (overload | neccessary. |
| protector, potential relay, start |
|
| and run capacitor) |
|
| - Faulty overload protector of | Check fan and replace if |
| condenser fan. | necessary. |
|
|
|
|
|
|