MINIMUM GAGE FOR CORD SETS
|
|
| Total Length of Cord in Feet (Meter) |
| |
|
| 0 – 25 | 26 – 50 | 51 – 100 | 101 – 150 |
|
| (0 – 7.6) | (7.9 – 15.2) | (15.5 – 30.5) | (30.8 – 45.7) |
Ampere |
| Rating |
| AWG |
|
More |
| Not More |
|
|
|
Than |
| Than |
|
|
|
0 | – 6 | 18 | 16 | 16 | 14 |
6 | – 10 | 18 | 16 | 14 | 12 |
10 | – 12 | 16 | 16 | 14 | 12 |
12 | – 16 | 14 | 12 | Not Recommended |
|
WARNING: Avoid electrical shock hazard. Never use this tool with a damaged or frayed electrical cord or extension cord.
Inspect all electrical cords regularly. Never use in or near water or in any environment where electric shock is possible.
GROUNDING INSTRUCTIONS
ALL GROUNDED,
Check with a qualified electrician or service personnel the grounding instructions are not completely understood, or if it doubt as to whether the tool is properly grounded.
Use only
Grounded, cord
GROUNDING METHODS
Fig. A | Fig. B | Fig. C |
Adapter
Metal Screw
Cover of Grounded
Outlet Box
Grounding Pin | Grounding Means |
SAVE THESE INSTRUCTIONS
AND
MAKE THEM AVAILABLE TO
OTHER USERS OF THIS TOOL!