GROUND FAULT CIRCUIT INTERRUPT (GFCI)

On HITACHI generator models (E43, E60, E71), all 20 Amp receptacles are protected by a ground fault circuit interrupt (GFCI). The GFCI shuts off the power to the receptacle when it senses small imbalances caused by current leakage to the ground.

TO TEST A GFCI: CAUTION: Each GFCI should be tested for proper operation every time the generator is used.

TO TEST A GFCI:

Start the generator. Turn the idle control switch (Fig.10-H) off. (See page10 for control panel layout information.) Push in the TEST button on the receptacle. The RESET button will pop out. Power is now off at the receptacle. If the RESET button does not pop out, the GFCI is not working.

Do not run generator until the problem can be corrected. To restore power to receptacle, push the RESET button in. If the RESET button pops out during operation, stop the generator and check the generator and equipment for defects.

REPLACEMENT PARTS

Fig.2

 

When servicing use only identical replacement parts.

Repairs should be conducted only by a Hitachi authorized service center.

USE PROPER EXTENSION CORD

Use only three-wire extension cords that have three-prong grounding-type plugs and three-pole receptacles that accept your tool’s or appliance’s plug. Replace or repair damaged cord.

Make sure your extension cord is in good condition. When using an extension cord, be sure to use one heavy enough to carry the current your product will draw. An undersized cord will cause a drop in line voltage resulting in loss of power and overheating. Be sure to choose a cord that will supply enough voltage to operate your tool or appliance. The tables below indicate appropriate guage for extension cords and the voltage drop caused by the use of extension cords, given different electrical loads.

MINIMUM GAGE FOR CORD SETS

Volts

Total Length of Cord in Feet (Meter)

 

 

 

 

120V

0 – 25

26

– 50

51 – 100

101

– 150

 

(0 – 7.6)

(7.9

– 15.2)

(15.5

– 30.5)

(30.8

– 45.7)

240V

0 – 50

51

– 100

101

– 200

201

– 300

 

(0 – 15.2)

(15.5

– 30.5)

(30.8

– 61.0)

(61.3

– 91.5)

Ampere Rating

 

AWG

 

More

 

Not More

 

 

 

Than

 

Than

 

 

 

0 – 10

16

16

14

14

10

– 13

16

16

14

12

13

– 16

14

14

12

12

16

– 25

12

12

12

10

25

– 30

10

10

10

Not Recommended

REPLACEMENT PARTSWARNING: Avoid electrical shock hazard. Never use this generator with a damaged or frayed electrical cord or extension cord.

Inspect all electrical cords regularly. Never use in or near water or in any environment where electric shock is possible.

SAVE THESE INSTRUCTIONS

AND

MAKE THEM AVAILABLE TO

OTHER USERS

AND

OWNERS OF THIS GENERATOR!