2-12. Electrical Service Guide

Input Voltage

200

230

400

460

575

 

 

 

 

 

 

Input Amperes At Rated Output

48

42

24

21

17

 

 

 

 

 

 

Max Recommended Standard Fuse Or Circuit Breaker Rating In Amperes

 

 

 

 

 

Circuit Breaker 1, Time-Delay 2

60

50

30

25

20

Normal Operating 3

70

60

35

30

25

Min Input Conductor Size In AWG/Kcmil

8

8

12

12

14

 

 

 

 

 

 

Max Recommended Input Conductor Length In Feet (Meters)

96

127

156

206

209

(29)

(39)

(47)

(63)

(64)

 

 

 

 

 

 

 

Min Grounding Conductor Size In AWG/Kcmil

8

10

12

12

14

 

 

 

 

 

 

Reference: 1999 National Electrical Code (NEC)

1Choose a circuit breaker with time-current curves comparable to a Time Delay Fuse.

2“Time-Delay” fuses are UL class “RK5” .

3“Normal Operating” (general purpose – no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and above).

YCaution: Failure to follow these fuse and circuit breaker recommendations could create an electric shock or fire hazard.

2-13. Selecting A Location And Connecting Input Power

18 in (457 mm) of space for airflow

YDo not move or operate unit where it could tip.

YAlways connect grounding conductor first.

= GND/PE

5

L1

L2

1 Rating Label

Supply correct input power.

2Plug (NEMA Type 6-50P)

3Receptacle

(NEMA Type 6-50R)

Connect plug to receptacle.

4Input And Grounding Conductors

Connect directly to line disconnect device if hard wiring is required.

5 Line Disconnect Device

See Section 2-12.

YSpecial installation may be required where gasoline or volatile liquids are present – see NEC Article 511 or CEC Section 20.