Honeywell MK VII FAULT ISOLATION TROUBLESHOOTING 3.1 GENERAL, Troubleshooting Guide, External

Models: MK VIII MK V MK XXII MK VII MK VI

1 68
Download 68 pages 50.96 Kb
Page 23
Image 23
3 FAULT ISOLATION (TROUBLESHOOTING)

EGPWS LINE MAINTENANCE MANUAL

3 FAULT ISOLATION (TROUBLESHOOTING)

3.1 GENERAL

The troubleshooting methods provided in this section identify system and sensor or subsystem faults to the lowest level possible. Additional fault isolation in the installation or associated sensors or subsystem should be performed using the aircraft installation and wiring diagrams and other supporting documentation in accordance with established maintenance procedures.

Do not remove or replace the EGPWC until all associated sensors or subsystems and their interfaces have been verified per established maintenance procedures and the fault is isolated to the EGPWC. If the troubleshooting methods determine that the EGPWC is faulty, then the EGPWC should be replaced per Section 6. Route the faulty EGPWC to an authorized repair facility for repair.

3.2 TROUBLESHOOTING GUIDE

In general, if any EGPWS Inoperative status is indicated, the EGPWC front panel LED’s should be checked. The following table shows the recommended maintenance action in response to the front panel LED’s.

EXTERNAL

COMPUTER

COMPUTER

 

FAULT

OK

FAIL

CORRECTIVE ACTION

 

 

 

 

OFF

GREEN

OFF

Normal operation.

YELLOW

GREEN

OFF

Troubleshoot external faults using the Level 2 Self-

 

 

 

Test. DO NOT REMOVE OR REPLACE THE EGPWC

OFF

OFF

OFF

Ensure that the EGPWC is installed in the rack

 

 

 

correctly and power to the EGPWC is turned on.

OFF

OFF

RED

Record the Level 2 Self-Test, if possible. Remove and

 

 

 

replace the EGPWC if required.

OFF

GREEN

RED

Record the Level 2 Self-Test, if possible. Remove and

 

 

 

replace the EGPWC if required.

YELLOW

OFF

OFF

Troubleshoot external faults using the Level 2 Self-

 

 

 

Test. DO NOT REMOVE OR REPLACE THE EGPWC

YELLOW

OFF

RED

Troubleshoot external faults using the Level 2 Self-

 

 

 

Test. Remove and replace the EGPWC if required.

YELLOW

GREEN

RED

Record the Level 2 Self-Test, if possible. Troubleshoot

 

 

 

external faults using the Level 2 Self-Test. Remove

 

 

 

and replace the EGPWC if required.

 

 

 

 

A Terrain INOP light rarely implies an external or internal failure of the EGPWC. The Terrain INOP light may turn on if the required accuracy of the position information is not being received from the GPS, IRS, or the FMC. Therefore, if the Terrain INOP light is reported to be on (or was on), perform a Level 2 Self-Test. If no faults are present, verify that position data from the GPS, IRS, or FMC is correct (note: this sentence does not apply to internal GPS engines).

NOTE: The Computer Fail Light will illuminate during some ground test procedures that use the WinVIEWS Software utility, even although no fault exists. The EGPWS Computer Fail Light will extinguish after testing has completed.

The following sections detail the operation of the EGPWS Self-Test and its use in troubleshooting EGPWS faults, when initiated by EGPWS Self-Test switches in the aircraft. Reference is made to a “short cancel” and a “long cancel”. A “short cancel” is defined as depressing the Self-Test switch (either in the cockpit or on the EGPWC front panel) for less than 2 seconds. A “long cancel” is defined as depressing the Self-Test switch (either in the cockpit or on the EGPWC front panel) for more than 2 seconds (but not longer than 59 seconds or a fault is indicated and Self- Test is exited). The affect of these is indicated in each section.

CAGE CODE: 97896

SCALE: NONE SIZE: A DWG NO.: 060-4199-180

REV: G

SHEET 23 of 68

Page 23
Image 23
Honeywell MK VII FAULT ISOLATION TROUBLESHOOTING 3.1 GENERAL, Troubleshooting Guide, Egpws Line Maintenance Manual, Fault