Hoshizaki DCM-500BWH-OS, DCM-500BAH-OS service manual Low Ice Production

Models: DCM-500BWH DCM-500BAH DCM-500BWH-OS DCM-500BAH-OS

1 69
Download 69 pages 4.5 Kb
Page 41
Image 41

Problem

Possible Cause

 

 

Remedy

 

 

 

 

 

 

[5] All components

d) Evaporator

1.

Defective.

1.

Replace.

run, but no ice is

 

 

 

 

 

e) Water Supply Line

1.

Condenser water

1.

Check and get

produced. (continued)

 

(water-cooled model

 

pressure too low or

 

recommended pressure.

 

only)

 

off and high pressure

 

 

 

 

 

control opens and

 

 

 

 

 

closes frequently.

 

 

 

f) Water Regulating Valve

1.

Water regulating

1.

Clean, adjust, or replace.

 

(water-cooled model

 

valve set too high or

 

 

 

only)

 

clogged (water-cooled

 

 

 

 

 

model only).

 

 

 

 

 

 

 

 

2. Low Ice Production

Problem

Possible Cause

 

 

Remedy

 

 

 

 

 

 

[1] Low ice production.

a)Evaporator

1.

Dirty or defective.

1.

Clean or replace.

 

b)Bin Control

1.

Erratic, sticking,

1.

Clean or replace.

 

 

 

defective.

 

 

 

 

 

 

 

 

 

c) Drain Valve

1.

Leaking water.

1.

Clean or replace.

 

 

 

 

 

 

 

d)Expansion Valve

1.

Bulb loose.

1.

Secure bulb.

 

 

 

 

 

 

2. Operating erratically.

2. Check and replace.

 

e)Refrigerant Charge

1.

Low charge.

1.

See "V.B. Service for

 

 

 

 

 

Refrigerant Lines."

 

 

 

 

 

 

2. Overcharge.

2. See "V.B. Service for

 

 

 

 

 

Refrigerant Lines."

 

 

 

 

 

 

 

f) Refrigerant Line

1.

Refrigerant line or

1.

Repair/replace the

 

 

 

component restricted.

 

clogged line/component

 

 

 

 

 

and replace the drier.

 

 

 

 

 

 

 

g)High-Side Pressure

1.

Dirty air filter or

1.

Clean.

 

Too High

 

condenser.

 

 

 

 

2. Ambient (or

2. Reduce temperature.

 

 

 

condenser) water

 

 

 

 

 

temperature too warm.

 

 

 

 

3. Fan motor slow rpm.

3. See "3. [2] a) Fan Motor."

 

 

 

 

 

 

4. Fan motor capacitor.

4. Check and replace.

 

 

 

 

 

 

5. Condenser water

5. Check and get

 

 

 

pressure too low or off

 

recommended pressure.

 

 

 

(water-cooled model

 

 

 

 

 

only).

 

 

 

 

 

 

 

 

6. Water regulating

6. Clean, adjust, or replace.

 

 

 

valve set too high or

 

 

 

 

 

clogged (water-cooled

 

 

 

 

 

model only).

 

 

 

h)Compressor

1.

Inefficient compressor.

1.

Replace

 

 

 

 

 

 

2. Faulty thermal

2. Replace compressor.

 

 

 

protector (overload).

 

 

 

 

 

 

 

 

3. Faulty capacitor/

3. Replace.

 

 

 

starter.

 

 

 

 

 

 

 

 

41