8)Check for leaks using nitrogen gas (140 PSIG) and soap bubbles.

9)Evacuate the system, and charge it with refrigerant. See the nameplate for the required refrigerant charge.

10)Attach the expansion valve bulb to the suction line in the same location as the previous bulb. The bulb should be at the 12 o'clock position on the tube. Be sure to secure the bulb with the clamp and holder and to insulate it.

11)Place the expansion valve cover in position.

12)Replace the panels in their correct positions.

13)Plug the unit back in.