5)Refill/Low Water Safety Cycle – As ice is produced, the water level in the reservoir drops. As it drops, the upper float switch and lower float switch open. The upper float switch opens first. Nothing occurs at this time. When the lower float switch opens, the refill begins. The water control relay
7)Shutdown – The bin fills and activates the bin control proximity switch. 90 seconds later the compressor and fan motor
the proximity switch opens. If the compressor and gear motor fail to stop, check the proximity switch and timer board relays.