2. BRAZING

2. BRAZING

WARNING

1.Refrigerant R22 itself is not flammable, explosive or poisonous. How- ever, when exposed to an open flame, R22 creates Phosgene gas, hazardous in large amounts.

2.Always recover the refrigerant and store it in an approved container. Do not discharge the refrigerant into the atmosphere.

3.Do not use silver alloy or copper alloy containing Arsenic.

Note: All brazing-connections in the Evaporator Case are clear-paint coated. Sandpaper the brazing-connections before unbrazing the components. Use a good abrasive cloth to remove paint.

3.REMOVAL AND REPLACEMENT OF COMPRESSOR IMPORTANT

Always install a new Drier every time the sealed refrigeration system is opened. Do not replace the Drier until after all other repair or replacement has been made.

Note: When replacing a Compressor with a defective winding, be sure to install the Start Capacitor, Run Capacitor and Start Relay supplied with the replacement Compressor.

1)Turn off the power supply.

2)Remove the panels.

3)Recover the refrigerant and store it in an approved container.

4)Remove the terminal Cover on the Compressor, and disconnect the Compressor Wiring.

5)Remove the Discharge and Suction Pipes using brazing equipment.

6)Remove the Hold-down Bolts, Washers and Rubber Grommets.