9.ADJUSTMENT OF WATER REGULATING VALVE - WATER-COOLED MODEL ONLY

The Water Regulating Valve (also called “WATER REGULATOR”) is factory-adjusted. No adjustment is required under normal use. Adjust the Water Regulator, if necessary, using the following procedures.

1)Attach a pressure gauge to the high-side line of the system. Or prepare a thermometer to check for the condenser drain temperature.

2)Rotate the adjustment screw by using a flat blade screwdriver, so that the pressure gauge shows the temperature specified in the table, 5 minutes after a freeze cycle or icemaking process starts. When the pressure exceeds 235 PSIG, or the condenser drain temperature exceeds the temperature range, rotate the adjustment screw clockwise. See Fig. 1.

3)Check that the pressure or the condenser drain temperature holds a stable setting.

CW - Lower

CCW - Higher

Fig. 1

MODEL

KML-200MWE

 

 

 

 

WATER TEMP. (°F)

50

70

90

 

 

 

 

AMBIENT TEMP. (°F)

 

 

 

 

 

 

 

70

100

100

105

80

99

105

105

90

99

105

105

100

100

105

105

 

 

 

 

41