the Series 8200zl | Switch |
Installing |
|
|
|
Installing the Series 8200zl Switch
Installation Procedures
| Installation Precautions (continued) |
|
|
C a u t i o n s | ■ If the switch is to be shipped in a rack, use only an HP 10000 series rack |
| and a rail mounting kit |
| supplies have been removed before shipping. |
| ■ Ensure the power source circuits are properly grounded, then use the |
| power cord supplied with the switch to connect it to the power source. |
| ■ If your installation requires a different power cord than the one supplied |
| with the switch and power supply, be sure the cord is adequately sized |
| for the switch’s current requirements. In addition, be sure to use a power |
| cord displaying the mark of the safety agency that defines the regulations |
| for power cords in your country. The mark is your assurance that the |
| power cord can be used safely with the switch and power supply. |
| ■ When installing the switch, note that the AC outlet should be near the |
| switch and should be easily accessible in case the switch must be |
| powered off. |
| ■ Ensure the switch does not overload the power circuits, wiring, and over- |
| current protection. Each power supply should be connected to a dedi- |
| cated branch circuit to prevent tripping building circuit breakers. To |
| determine the possibility of overloading the supply circuits, add together |
| the ampere ratings of all devices installed on the same circuit as the |
| switch and compare the total with the rating limit for the circuit. The |
| maximum ampere ratings are usually printed on the devices near the AC |
| power connectors. |
| ■ Do not install the switch in an environment where the operating ambient |
| temperature might exceed 40°C (104°F). |
| ■ Allow three to four inches of space around the sides and back of the |
| switch to make sure the air flow for the switch is not restricted. |
|
|
|
|