9.Unscrew the plastic screw cap that secures the sensor to the flow meter.

10.Remove the sensor from the flow meter.

11.Disconnect the flow meter sensor cable from the water controller.

12.Remove the flow meter sensor cable from the cable wrap bundle, and remove the flow meter sensor and cable from the MCS G2 unit.

Replacing the flow meter sensor

1.Align the notch of the flow meter sensor to the keyed notch of the flow meter.

Removal and replacement procedures 40