Parameter | Range |
|
|
Specific conductance at 25ºC | |
(77ºF) |
|
|
|
Alkalinity ("M" as CaCO3) | |
Sulfur (SO4) | |
Chloride (Cl) | |
|
|
Hardness (CaCO3) | |
Calcium hardness (CaCO3) | |
Magnesium hardness (CaCO3) | |
Copper (Cu) | < 0.20 ppm |
|
|
Iron (Fe) | < 3.0 ppm |
|
|
Aluminum (Al) | < 0.50 ppm |
|
|
Sodium (Na) | |
|
|
Silica (SiO2) | |
Zinc (Zn) | < 1.0 ppm |
|
|
Manganese (Mn) | < 0.1 ppm |
|
|
Phosphate Ortho- (Po4) | < 3 ppm |
Bacteria | < 1000 CFU/ml |
|
|
Suspended solids | < 10 ppm |
|
|
If your water is out of range, consult a water quality expert.
HP recommends using particulate filtration on the dedicated water supply system connected to the HP Modular Cooling System G2 unit.
Frost damage
To avoid frost damage, the water temperature must not be allowed to fall below the minimum permissible temperature of +4 ºC (+39.2 ºF) at any point in the water cycle.
Before storage or transportation at
Water precautions
Take the following precautions during the installation of the MCS G2 unit:
•Before installing the HP Modular Cooling System G2
•Evaluate the
•Ensure that the chilled water loop is properly designed for liquid cooling systems and is separate from the sanitary water systems in your building (bathroom, sink, drinking water, and so on).
Maintenance 76