b.Using a T-25 Torx driver, remove the four T-25 Torx screws at each corner that secure the water group cover to the MCS G2 unit.

5.Remove the condensation pump ("Removing the condensation pump" on page 30).

6.Using a T-25 Torx driver, remove the two T-25 sheet metal screws securing the sensor bracket to the MCS G2 unit (1).

7.Remove the sensor bracket and attached water level sensors from the MCS G2 unit (2).

8.Remove the cable ties and unwrap the cable harness.

9.Disconnect the water level sensor cables from the water controller.

Replacing the water level sensors

1.Connect the water level sensor cable to the water controller.

2.Align the sensor bracket to the appropriate holes in the MCS G2 unit (1).

Removal and replacement procedures 62