ADDITIONAL UPS FEATURES

Port

To establish communication between the UPS and a computer, connect your computer to the UPS serial port using the supplied communication cable.

When the communication cable is installed, HP Power Manager software can exchange data with the UPS. The software polls the UPS for detailed information on the status of the power environment. If a power emergency occurs, the software initiates the saving of all data and an orderly shutdown of the equipment.

The cable pins are identified in Figure 16, and the pin functions are described in Table 2.

UPS Rear Panel

6

7

 

8

9

1

2

3

4

5

 

 

Figure 16 Serial Port

 

Table 2

Serial Port Pin Assignment

 

 

 

 

 

Pin

Signal Name

Function

Direction from

Number

the UPS

 

 

 

 

 

 

1

Low Batt

Low battery relay contact; 20 mA, 30 Vdc

Out

 

 

contact rating

 

 

 

 

 

2

TxD

Transmit to external device

Out

 

 

 

 

3

RxD

Receive from external device

In

 

 

 

 

4

DTR

PnP (Plug and Play) from external device

In

 

 

(tied to Pin 6)

 

 

 

 

 

5

GND

Signal common (tied to chassis)

 

 

 

 

6

DSR

To external device (tied to Pin 4)

Out

 

 

 

 

7

No connection

 

 

 

 

8

AC Fail

AC fail relay contact; 20 mA, 30 Vdc

Out

 

 

contact rating

 

 

 

 

 

9

Power Source

+V (8 to 24 volts DC power)

Out

 

 

 

 

HP T750 G2, HP T750J, HP T1000 G3, HP T1000J, HP T1500 G3, and HP T1500J UPS Models User Guide S 505922-002

15

Page 22
Image 22
HP T750 G2, T1000 G3, T1000J, T1500 G3, T750J, T1500J manual Serial Port Serial Port Pin Assignment