SPECIFICATIONS
Table 8 Battery
UPS Configuration | HP T750 G2: (2) 12V, 7 or 7.2 Ah internal batteries |
| HP T750J and HP T1000 G3: (2) 12V, 9 Ah internal batteries |
| HP T1000J, HP T1500 G3, and HP T1500J: (3) 12V, 9 Ah internal batteries |
|
|
Voltage | HP T750 G2, HP T750J, and HP T1000 G3: 24 Vdc |
| HP T1000J, HP T1500 G3, and HP T1500J: 36 Vdc |
|
|
Type | Sealed, maintenance‐free, valve‐regulated, lead‐acid |
|
|
Charging | Advanced charging for faster recovery; approximately 3 hours to 90% usable capacity at nominal line |
| and no supplementary power supply load |
|
|
Monitoring | Advanced monitoring for earlier failure detection and warning |
|
|
Table 9 Battery Runtimes (in Minutes)
|
|
| UPS Models by VA Ratings |
|
|
|
|
|
|
Load (VA) | Watts | 750 | 1000 | 1400 |
|
|
|
|
|
200 | 128 | 38 | 41 | 58 |
|
|
|
|
|
300 | 192 | 27 | 28 | 41 |
|
|
|
|
|
500 | 320 | 14 | 15 | 28 |
|
|
|
|
|
600 | 402 | 9 | 10 | 19 |
|
|
|
|
|
750 | 503 | 6 | 8 | 14 |
|
|
|
|
|
900 | 603 |
| 6 | 10 |
|
|
|
|
|
1000 | 670 |
| 5 | 8 |
|
|
|
|
|
1200 | 804 |
|
| 6 |
|
|
|
|
|
1400 | 938 |
|
| 5 |
|
|
|
|
|
NOTE Battery times are approximate and may vary depending on the load configuration and battery charge.
26 | HP T750 G2, HP T750J, HP T1000 G3, HP T1000J, HP T1500 G3, and HP T1500J UPS Models User Guide S |