SPECIFICATIONS

Table 8 Battery

UPS Configuration

HP T750 G2: (2) 12V, 7 or 7.2 Ah internal batteries

 

HP T750J and HP T1000 G3: (2) 12V, 9 Ah internal batteries

 

HP T1000J, HP T1500 G3, and HP T1500J: (3) 12V, 9 Ah internal batteries

 

 

Voltage

HP T750 G2, HP T750J, and HP T1000 G3: 24 Vdc

 

HP T1000J, HP T1500 G3, and HP T1500J: 36 Vdc

 

 

Type

Sealed, maintenance‐free, valve‐regulated, lead‐acid

 

 

Charging

Advanced charging for faster recovery; approximately 3 hours to 90% usable capacity at nominal line

 

and no supplementary power supply load

 

 

Monitoring

Advanced monitoring for earlier failure detection and warning

 

 

Table 9 Battery Runtimes (in Minutes)

 

 

 

UPS Models by VA Ratings

 

 

 

 

 

 

Load (VA)

Watts

750

1000

1400

 

 

 

 

 

200

128

38

41

58

 

 

 

 

 

300

192

27

28

41

 

 

 

 

 

500

320

14

15

28

 

 

 

 

 

600

402

9

10

19

 

 

 

 

 

750

503

6

8

14

 

 

 

 

 

900

603

 

6

10

 

 

 

 

 

1000

670

 

5

8

 

 

 

 

 

1200

804

 

 

6

 

 

 

 

 

1400

938

 

 

5

 

 

 

 

 

NOTE Battery times are approximate and may vary depending on the load configuration and battery charge.