WARNING!! ERROR CONDITION 2: if the

7520 uses the same DC

 

power

ground with

Host

PC/PLC (for

example,

Host PC/PLC

 

provide non-isolated DC power source to 7520). In this situation,

 

 

(1)

The

Host PC/PLC is common ground with power ground of

7520

 

(2)

The power ground of

7520 is common ground with

RS-485

 

 

 

 

 

 

 

 

Therefore the

Host PC/PLC is common ground with

RS-485 network.

That is to say, there is no isolation between Host PC/PLC and

RS-485

network. So

the

Host PC/PLC may be

damaged

if there is high voltage

transient on

RS-485 network.

 

 

 

 

 

 

 

 

 

 

OK CONDITION: If the DC power ground of

7520 or

7520R is not common

 

 

to any module, the

Host PC/PLC will be isolated from

RS-485 network in

 

 

all conditions.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The power adapter PWR-24 is designed for single 7000 series modules only. The 24V DC output of the PWR-24 is isolated from its AC input. If the 7520 or 7520R is connected to the PWR-24, this PWR-24 cannot connect to the other module. Normally the Host PC/PLC uses a switching power and the DC output of this power supply is also isolated from its AC input. Therefore the DC power ground of 7520 or 7520R is isolated from Host PC/PLC. Therefore, the Host PC/PLC is isolated from RS-485 network in all condition.

PWR-24

￿7520

￿RS-232 ￿7520R ￿RS-485

￿Host PC/PLC

Connecting 256

 

modules without

 

 

repeater, 7510

 

 

￿7000 series

￿7000 series

￿Host PC/PLC is isolated from ￿RS-485 network for ￿7520 or ￿7520R in all condition

7000 Bus Converter User Manual (version 1.2,Feb/2003, 7PH-006-10) ---------------

25

Page 25
Image 25
ICP DAS USA 7000 user manual Uses the same DC, Power Ground with Host PC/PLC for, If there is high voltage