For example, the ￿7510, ￿7510, ￿7510 are used to isolate local modules from ￿RS-485 network. If there is high energy transient on ￿RS-485 network, all the local modules will be safe.

Isolation Configuration (Strongly Recommended)

 

 

 

Host

R

RS232

7520

￿RS-485

 

RS485

￿7510

￿RS-485

T

 

D+

 

 

D+

 

PC

 

D-

 

 

 

D-

 

 

RS485

 

 

 

 

PLC

 

 

 

 

RS485

 

 

 

GND

 

7xxx

 

 

 

7xxx

 

Is terminator

 

 

 

 

 

 

￿7510

￿7510

 

￿7510

 

 

 

 

RS485

 

RS485

 

RS485

 

 

￿Group A

 

￿Group B

 

￿Group C

 

 

 

 

RS485

RS485

 

RS485

 

 

 

 

 

 

 

 

7xxx

 

7xxx

 

7xxx

 

 

 

7xxx

 

7xxx

 

7xxx

 

If the RS-485 network is not over 100 meters, the terminated resistors are not needed. However, it may be necessary to insert two terminated resistors at both end of the RS-485 segment. It is not easy to calculate the value of a terminator resistor. The best way to do this is to use an oscilloscope to check the RS-485 signal directly. If the impedance match of RS-485 network is OK, the oscilloscope will show a very nice square wave. If these square wave signals are distorted, the user will need to insert two terminators at both end of the RS-485 segment.

OK

Resistor

value

of

Resistor value of

 

terminator is too small

terminator is too big

 

 

 

 

 

7000 Bus Converter User Manual (version 1.2,Feb/2003, 7PH-006-10) --------------- 75