rates are different. For example, 7xxx=module address 01, baud rate=1200 7xxx=module address 01, baud rate=9600 7xxx=module address 01, baud rate=115200
These three modules can share the same
(4)Therefore there is 256*8=2048 modules max. In one
The “search function” given in NAP7000S can search for all these 2048
modules in one
When the
The power ground of the 7000 series is common ground to the RS-
485 network. This feature is the same as the Adam 4000, Nudam 6000
and DATAFORTH 9B series. Therefore all the modules in the same RS-
485 network are common ground. For example, the all modules between 7xxx and 7xxx share the same
network noise by high energy transient in this environment. If this noise is
too great, all the modules in the
simultaneously. This is highly possible and occurs often in real world applications. It is strongly recommended to add another isolation repeater, the 7510, to break the long path
This is the third function of 7510.