7.Quick Starting the 7000 Series

7.1Find Status of Unknown Module

Wire connection: Refer to Sec. 2.7

Test program: Refer to “NAP7000S User Manual” for TEST.EXE

Connect I NIT*_pin to GND_pin first as follows.

The steps to finding the status of an unknown module are given as follows.

1.Wire connection, INIT*_pin=GND, power on and run test.exe

2.Press 2

3.

Press $002[Enter]

Receive=! 02080A40

4.

Press 2

 

5.

Press %0001080600[Enter] Receive=! 01

6.Power off, disconnect INIT*_pin (pin 6) and GND_pin (pin_10) and power on

7.Press 2

8.

Press $012[Enter]

Receive=! 01080600

9.

Press 2

 

10. Press $01M[Enter]

Receive=! 017017

11.

Press 2

 

12. Press $01F[Enter]

Receive=! 01A1.3

 

Step 3: read the

module status with the INIT*_pin connected to the

GND_pin and find that module address=02, baud rate= 115200, checksum is enable.

Step 5: change this module to address=01, baud rate=9600, checksum

disable

Step 6-12: disconnect the INIT*_pin and read back the module status

NOTE: If the INIT*-pin is connected to GND-pin, the 7xxx will go to its default setting as follows:

(1)Module address=00; (2) baud rate=9600; (3) checksum is disable