368262-UIM-B-1008

Table 6: Ratings & Physical / Electrical Data

 

Input

 

Output

Nominal

Air Temp. Rise

Air Temp. Rise

Max/Min

 

Max/Min

Airflow

Max Input

Min Input

MBH

 

kW

MBH

 

kW

CFM

m3/min

°F

°C

°F

 

°C

60/30

 

17.6/8.8

47/24

 

13.8/7.0

1200

34.0

30-60

17-33

20-50

 

11-28

80/40

 

23.5/11.8

62/32

 

18.2/9.4

1200

34.0

40-70

22-39

20-50

 

11-28

80/40

 

23.5/11.8

62/32

 

18.2/9.4

1600

45.3

35-65

19-36

20-50

 

11-28

100/50

 

29.3/14.7

78/40

 

22.8/11.7

1600

45.3

35-65

19-36

20-50

 

11-28

100/50

 

29.3/14.7

78/40

 

22.8/11.7

2000

56.6

35-65

19-36

20-50

 

11-28

120/60

 

33.7/16.9

95/48

 

27.8/14.1

2000

56.6

45-75

25-42

25-55

 

13-31

Max.

Outlet

 

Blower

Blower

AFUE

Max

Total Unit

Min. wire Size

Air Temp

 

Wheel

Over-Current

(awg) @ 75 ft

 

 

 

%

Amps

°F

 

°C

HP

 

Amps

size

Protect

one way

 

 

 

 

160

 

71.1

1/2

 

4.8

11 x 8

80.0

15

7.0

 

14

170

 

76.7

1/2

 

4.8

11 x 8

80.0

15

7.5

 

14

165

 

73.9

3/4

 

7.5

11 x 10

80.0

15

10.0

 

14

165

 

73.9

3/4

 

7.5

11 x 10

80.0

15

10.0

 

14

165

 

73.9

1

 

14.5

11 x 11

80.0

20

12.0

 

12

175

 

79.4

1

 

14.5

11 x 11

80.0

20

12.0

 

12

Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test procedures.

Wire size and over current protection must comply with the National Electrical Code (NFPA-70-latest edition) and all local codes.

SUPPLY VOLTAGE CONNECTIONS

Junction Box

Connect ground lead to screw

Electrical Entry

L1-Hot BLK

Neutral WHT

FIGURE 18: Electrical Wiring

1.Provide a power supply separate from all other circuits. Install overcurrent protection and disconnect switch per local/national electrical codes. The switch should be close to the unit for conve- nience in servicing. With the disconnect or fused switch in the OFF position, check all wiring against the unit wiring label. Refer to the wiring diagram in this instruction.

2.Remove the screws retaining the wiring box cover. Route the power wiring through the opening in the unit into the junction box with a conduit connector or other proper connection. In the junc- tion box there will be 3 wires, a Black Wire, a White Wire. Connect the power supply as shown on the unit-wiring label on the inside of the blower compartment door or the wiring schematic in this sec- tion. The black furnace lead must be connected to the L1 (hot) wire from the power supply. The white furnace screw must be con- nected to neutral. Connect the power supply ground to the green screw (equipment ground) An alternate wiring method is to use a field provided 2” (5.1 cm) x 4” (10.2 cm) box and cover on the out- side of the furnace. Route the furnace leads into the box using a protective bushing where the wires pass through the furnace panel. After making the wiring connections replace the wiring box cover and screws. Refer to Figure 18.

3.The furnace's control system requires correct polarity of the power supply and a proper ground connection. Refer to Figure 18.

The power connection leads and wiring box may be relocated to the left side of the furnace. Remove the screws and cut wire tie holding excess wiring. Reposition on the left side of the furnace and fasten using holes provided.

LOW VOLTAGE CONTROL WIRING CONNECTIONS

Install the field-supplied thermostat by following the instructions that come with the thermostat. With the thermostat set in the OFF position and the main electrical source disconnected, connect the thermostat wiring from the wiring connections on the thermostat to the terminal board on the ignition module, as shown in Figures 19-24, Thermostat Charts. Electronic thermostats may require the common wire to be con- nected as shown in Figure 16. Apply strain relief to thermostat wires passing through cabinet.

Set the heat anticipator in the room thermostat to 0.1 amps. Setting it lower will cause short cycles. Setting it higher will cause the room temperature to exceed the set points.

Some electronic thermostats do not have adjustable heat anticipa- tors. They should be set to six cycles per hour. Follow the thermo- stat manufacturer's instructions.

The 24-volt, 40 VA transformer is sized for the furnace components only, and should not be connected to power auxiliary devices such as humidifiers, air cleaners, etc. The transformer may provide power for an air conditioning unit contactor.

AIR CONDITIONER CONNECTIONS

This furnace may be used with single-stage or two-stage air condition- ing units.

For Single-Stage A/C - Connect the low voltage wiring as shown in Figure 19, Thermostat Chart.

For Two-Stage A/C - Use a two-stage thermostat, connect the low volt- age wiring as shown in Figure 20, Thermostat Chart.

For Two-Stage A/C using a Single-Stage Thermostat - connect the low voltage wiring as shown in Figure 20, Thermostat Chart.

This furnace control board can control a two-stage A/C using only a sin- gle-stage thermostat. In this case, the furnace control switches between high cool and low cool based on the calculated cooling load.

12

Johnson Controls Unitary Products

Page 12
Image 12
Johnson Controls YP8C/YPLC*MP, LP8C/LPLC*MP Supply Voltage Connections, LOW Voltage Control Wiring Connections, Max Outlet