THERMAL EXPANSION

Water supply systems may, because of such events as high line pressure, frequent cut-off_, the effects of water hammer among others, have installed devices such as pressure reducing valves, check valves, back flow preventers, etc.-to control these types of _roblems. When these devices are not equipped with an internal

y-pass, and no other measures are taken, the devices cause the water system to be dosed. As water is heated, it expands (ther-

mal expansion) and closed systems do not allow for the expan- sion of heated water.

The water within the water heater tank expands as it is heated and increases the pressure of the water system. If the relieving point of

the water heater's temperature-pressure relief valve is reached, the

valve will relieve the excess pressure. The temperature-pressurerelief valve is not intended for the constant relief of thermal

expansion. This is an unacceptable condition and must be cor- rected.

It is recommended that any devices installed which could create a closed system have a by-pass and/or the system have an expan- sion tank to relieve the pressure built by thermal expansion. Thermal expansion tanks are available from Sears stores and through the Sears Service Centers. Contact the local plumbing inspector, water supplier and/or the Sears Service Center for assistance in controlling these situations.

HOT

COU_ WATER

HEATER

(3)

 

- COLD

WATER

PRESSURE

 

INLET

FITTING

REDUCING

 

 

 

VALVEWITH

 

 

 

BY-PASS

 

EXPANSION

 

 

TANK(0

1

(z)

PRESSUREGAUGE

WATER

SHUTOFF

RECOMMENDED INSTALLATION

(VERTICAL MOUNTING)

 

WATER HEATER

FLOOR, CEILING

 

COLD WATER

JOIST, ETC.

 

INLET FITTING

 

HOT

COLD

STRAPPING

Thermal Expansion Tank Specifications

Model

_lhnk Capacity

Dimensions

in Inches

Pipe Fitting

Number

In Gallons

Diameter

Length

On

"Ihnk

153.331020

2

 

8 inches

12_ inches

74"Male

153.331050

5

 

11 inches

14_ inches

74"Male

Expansion

Tank

Sizing Chart

 

 

 

 

Inlet*

 

Water Heater Capacity

(Gallons)

 

Water

 

 

 

 

 

Expansion

Pressure

30

40

50

66

80

40psi

2

2

2

5

5

_nk

Capacity

50psi

2

2

2

5

5

Needed

60psi

2

2

5

5

5

 

70psi

2

2

5

5

5

 

80psi

2

5

5

5

5

*Highest recorded inlet water pressure in a 24 hour period or regulated water pressure.

NOTE: Expansion tanks are pre-charged with a 40 psi air

charge.. If the inlet,. water pressure is higJ.her than 40 psi, the expansmn tanks a_r pressure must be adjusted to match that

pressure, but must not he higher than 80 psi.

(3)

PRESSURE

REDUCING INLETCOLD

VALVEWITH WATER

O)BY-PASS SHUTOFF

EXPANSION

TANK

(z)_

PRESSUREGAUGE

ALTERNATE RECOMMENDED

INSTALLATION

(HORIZONTAL MOUNTING)

STRANGE SOUNDS

Possible noises due to expansion and contraction of some metal _arts during periods of heat-up and cool-down do not represent

armful or dangerous conditions.