Installation Instructions
Step 2
Wiring Instructions:WIRING REQUIREMENTS•This smoke alarm should be installed on a U.L. listed or rec- ognized junction box. All connections should be made by a qualified electrician and all wiring used shall be in accordance with articles 210 and 300.3(B) of the U.S. National Electrical Code ANSI/NFPA 70, NFPA 72 and/or any other codes having jurisdiction in your area. The multiple station interconnect wiring to the alarms must be run in the same raceway or cable as the AC power wiring. In addition, the resistance of the interconnect wiring shall be a maximum of 10 ohms.
•The appropriate power source is 120 Volt AC Single Phase supplied from a
•Smoke alarms are not to be used with detector guards unless the combination (alarm and detector guard) have been evalu- ated and found suitable for that purpose.
•WARNING: The alarm cannot be operated from power derived from a square wave, modified square wave or modi- fied sine wave, inverter. These types of inverters are some- times used to supply power to the structure in off grid instal- lations, such as solar or wind derived power sources. These power sources produce high peak voltages that will damage the alarm.
WIRING INSTRUCTIONS FOR AC QUICK CONNECT HARNESSCAUTION! TURN OFF THE MAIN POWER TO THE CIRCUIT BEFORE WIRING THE ALARM.•For alarms that are used as single station, DO NOT CONNECT THE RED WIRE TO ANYTHING. Leave the red wire insulating cap in place to make certain that the red wire cannot contact any metal parts or the electrical box.
•When alarms are interconnected, all interconnected units must be powered from a single circuit.
11