TP-6069 6/0320 Section6 Electrical System
Amps
Max.
Voltage
Number
of Poles Model(s)
2
0
250 1 4EFOZ
2
0
600 3 8.5/11.5EFOZ,14EOZ
22 250 2 4EFOZ, 5EOZ
25 250 2 5EOZ
2
5
0
16.5EFOZ
3
0
2
5
0
26.5EFOZ
3
0
600 3 11.5/17.5/20EFOZ,
14/20/24EOZ—3 phase
33 250 2 8EOZ
3
5
2
5
0
14EFOZ
3
5
2
5
0
28EOZ
250 1 5EOZ
40 600 3 11.5E FOZ,
14/20/24EOZ—3 phase
4
2
2
5
0
19EFOZ
4
2
2
5
0
29EFOZ, 8/10EOZ
2
4
0
111/13EFOZ
2
4
0
211/11.5/17.5EFOZ
50 250 2 9EFOZ,10EOZ
480 3 20/23/27EFOZ,
20/28/32EOZ—3 phase
55 250 1 5EOZ
2
4
0
113EFOZ
2
4
0
211/13EFOZ,13/14EOZ
60 250 1 6.5EFOZ
600 3 17.5/20EFOZ,
20/24/28/32EOZ—3 phase
2
4
0
116EFOZ
7
0
2
4
0
213/20EFOZ, 15.5EOZ
7
0
250 1 6.5EFOZ, 8EOZ
600 3 20/24EOZ—3 phase
116/19EFOZ
80
240 216EFOZ, 20EOZ—1 phase,
20/24EOZ—3 phase
8
0
250 1 8EOZ
480 3 23EFOZ—3 phase
85 250 1 9EFOZ,10EOZ
119EFOZ
90 240 219EFOZ—1 phase
20/23EOZ
480 3 27EFOZ—3 phase
240 2 23EOZ
100 480 3 23/27EFOZ,
28/32EOZ—3 phase
1
2
5
6
0
0
223/27EFOZ, 28EOZ—
1 phase, 27EFOZ—3 phase
1
2
5
6
0
0
323/27EFOZ,
28/32EOZ—3 phase
150 600 2 28/32EOZ—1 phase,
32EOZ— 3 phase
175 600 2 32EOZ—1 phase
Figure 6-2 AC Circuit Breaker Ratings (4--27EFOZand 5--32EOZModels), Listed By Amps
Amps
Max.
Voltage
Number
of Poles Typ e Model(s)
60 600 3 UL/IEC 33EFOZ, 40EOZ
70 600 3 UL/IEC 40EFOZ, 40EOZ
80 480 3 UL/IEC 40EFOZ, 50EOZ
100 480 3 UL/IEC 55EFOZ, 50/65EOZ
100--125 600 3 IEC 33/55EFOZ,
40/65EOZ
100--125 600 3 IEC 70EFOZ,80EOZ
125 600 3 UL 33/55EFOZ,
40/65EOZ
125 600 3 UL 70EFOZ, 80EOZ
128--160 600 3 IEC 33/40EFOZ,
40/50EOZ
128--160 600 3 IEC 70/80EFOZ,
80/99EOZ
150 600 3 UL 33/40EFOZ,
40/50EOZ
150 600 3 UL 70/80EFOZ,
80/99EOZ
160--400 600 3 UL 70/80/100EFOZ,
80/99/125/150EOZ
160--400 600 3 IEC 70/80/100/125EFOZ,
80/99/125/150EOZ
200 600 3 UL 40/55EFOZ,
50/65EOZ
200 600 3 UL 100EFOZ,
99/125EOZ
200--250 600 3 IEC 40/55EFOZ,
50/65EOZ
200--250 600 3 IEC 70/100/125EFOZ,
80/125/150EOZ
240--600 600 3 UL 125EFOZ,
125/150EOZ
250 600 3 UL 55EFOZ, 65EOZ
250 600 3 UL 70/125EFOZ,
80/125/150EOZ
250--630 600 3 IEC 125EFOZ,
125/150EOZ
Figure 6-3 AC Circuit Breaker Ratings (33--150kWModels), Listed By Amps

Accidental starting.

Can cause severe injury or death.

Disconnectthe battery cables before

working on the generator set.

Remove the negative (--) lead first

when disconnecting the battery.

Reconnect the negative (--)lead last

when reconnecting the battery.

WARNING