10.Connect the side of the circuit breaker marked LOAD to the ship-to-shore switch or craft wiring. Attach insulation boots to the black leads if the kit includes insulation boots. With a single-pole circuit breaker use one black lead (L1). With a two-pole circuit breaker use two black leads, L1 and L2. Connect the neutral (white) lead to the L0 stud. Connect the equipment ground (green) lead to GRD stud.

Note: Wire material. Use stranded copper for all wiring. Use wire gauges and insulation, conductor temperature ratings, sheath stripping, conductor support and protection, conductor terminals and splices, and overcurrent protection (circuit breakers, fuses) that conform to standards and codes.

Note: Follow USCG Regulations CFR33, Part 183 (Pleasurecraft) and CFR46 (Commercial Craft) for marine applications.

Note: Wire protection. Use rubber grommets and cable ties as necessary to protect and secure wiring from sharp objects, the exhaust system, and any moving parts.

11.Replace the controller cover or circuit breaker box access panel.

12.Reconnect the generator set engine starting battery, negative (--) lead last.

13.Make voltage or frequency adjustments according to Section 8.

Note: Voltage/frequency adjustable. Some four-lead generator sets are not voltage/frequency adjustable. To determine adjustment possibilities, check the model’s specification sheet or service manual. If you are reconnecting the generator set from a single-voltage to a dual-voltage configuration (example: from 120-volt to 120/240-volt) or a dual voltage to a single voltage (example: from 120/240-volt to 120-volt) with the same primary voltage, do not adjust the voltage/frequency adjustment. Adjust the voltage/frequency for frequency changes or setting changes of the primary voltage (example: from 120-volt to 100-volt). Refer to the model’s specification sheet for reconnection capability.

6.2.3Circuit Breaker Installation (33--125EFOZ and 40--150EOZ Models)

1.Place the generator set master switch in the OFF position.

2.Disconnect the generator set engine starting battery, negative (--) lead first.

3.Remove the six screws from the right side junction box panel and remove the panel.

4.Install the circuit breaker on the new panel with the screws and washers. Position the ON side of the circuit breaker toward the rear of the junction box. See Figure 6-4.

5.Attach stator leads L1, L2, and L3 to the extension leads (if supplied) or to the line side of the circuit breaker. See Figure 8-5.

Note: Insulate leads with electrical tape after connecting extension leads to stator leads.

6.Connect the neutral connection stator leads to the L0 stud.

Note: Verify that terminal positions and previously made line lead connections allow room for load connections to load studs.

7.Connect the load side of the circuit breaker to customer-supplied craft wiring. Connect the neutral lead to the L0 stud. See Figure 8-5.

8.Attach the new panel to the junction box using the original six screws. See Figure 6-4.

9.Check that the generator set master switch is in the OFF position. Reconnect the generator set engine starting battery, negative (--) lead last.

22 Section 6 Electrical System

TP-6069 6/03

Page 32
Image 32
Kohler 16EFOZ/20EOZ, 8.5EFOZ, 9EFOZ/10EOZ, 80EFOZ/99EOZ, 6.5EFOZ/8EOZ, 4EFOZ/5EOZ, 40EFOZ/50EOZ Electrical System TP-6069 6/03